Starting Up - HindlePower ATevo Series Operating/Service Instructions Manual

Hide thumbs Also See for ATevo Series:
Table of Contents

Advertisement

HindlePower Inc
4.1.4.

4.1.4. Starting Up

Starting Up
After confirming that all connections to ATevo are properly made, start up as follows:
1. Turn ON (close) AC Input Circuit Breaker (CB1) first.
You should hear a soft hum from ATevo as output increases. ATevo LCD should start up and
indicate dc output voltage. If the display does not light, do not proceed. Turn OFF (open)
the AC Breaker (CB1) and recheck connections.
!
If you attempt to turn ON the DC Output Circuit Breaker (CB2) first, it may trip
due to the filter capacitor in-rush.
2. Turn ON (close) the DC Output Circuit Breaker (CB2).
If any error codes or alarms appear on the Main ATevo Display and/or Alarm Indicator LEDs,
refer to
Section 8, Alarms & Indicators
indication before proceeding.