HindlePower Inc
5.2.
5.2. High Voltage Shutdown
High Voltage Shutdown
ATevo has a High Voltage Shutdown feature similar to the High Voltage Shutdown feature in
legacy AT10.1 chargers. With this software feature the Main Control Board (A1) monitors the dc
voltage and will turn OFF the output drivers (rectifier controllers) if the dc output voltage is too
high.
Output voltage must exceed and stay above the High DC Voltage Alarm set point for 30
seconds in order for High Voltage Shutdown to occur. If it does, the High Voltage Shutdown
Alarm and the Common Alarm Relay are activated. ATevo must be restarted with both AC and
DC circuit breakers to clear the shutdown and turn ON the rectifier controls.
The High Voltage Shutdown feature can be enabled or disabled as described in
*
ATevo also has a har
Section 5.4.
Copyright HindlePower Inc. 2021
hardwar
dware e High Level Detect (analog) feature that is described in
ATevo O&SI - 1PH Input Group I (6-25 Adc) - 1.1_en
Last modified: 8 September 2023
Section
4.3.2.
Page 134 of 316