HindlePower ATevo Series Operating/Service Instructions Manual page 186

Hide thumbs Also See for ATevo Series:
Table of Contents

Advertisement

HindlePower Inc
8.2.
8.2. Hindle Health System –
Hindle Health System –
Components
Components
The Hindle Health System is composed of four (4) major components:
• Self-Diagnostics utility running in the background
• Hindle Health Button
• Hindle Health LEDs
• Hindle Health Screens
8.2.1 Self-Diagnotics Utility (runs in background)
8.2.1 Self-Diagnotics Utility (runs in background)
ATevo microprocessors continuously run utilities that check hardware component operation
including: memory, communications interfaces, parameters, and discrete devices such as
relays.
They also test that all input values and measurements are within tolerance of reasonable
ranges. Some critical parameters such as dc voltage and dc current are sampled by multiple
processors and have redundant qualification requirements. Any errors detected are reported
immediately by alarms and/or status updates. The utilities provide possible causes and
proposed solutions to resolve issues found.
8.2.2 Hindle Health Button
8.2.2 Hindle Health Button
The Hindle Health Button is on the lower-right corner of the control panel overlay. When
pressed, it starts the user-assisted portion of the Hindle Health System. This process will check
areas of the battery charger that the continuous self-diagnostics cannot. For example, ATevo
cannot test a relay's performance without forcing it to change state. The user will be guided
through the test procedure via the Hindle Health Screens described later in this Section.
8.2.3 Hindle Health
8.2.3 Hindle Health LED
Hindle Health LED Indicators are at the bottom of the front panel overlay.
• GREEN LED , when lit, indicates ATevo is healthy.
• RED LED , when lit, indicates ATevo has an issue. Urgency of action required depends
upon if it is:
Blinking
Blinking
– Immediately replace Main Ctrl Board (A1). There is a critical failure of the
microprocessor driving the display and front panel controls. LCD display may be
blank, frozen, or displaying corrupted data. Core microprocessor responsible for
charging the battery may still be operational.
Solid
Solid
– ATevo requires attention, but the condition is not critical. In most cases, LCD
display will operate and be able to report the issue and give instructions on how to
Copyright HindlePower Inc. 2021