8.3.
8.3. Hindle Health System – Screens
Hindle Health System – Screens
Hindle Health System screens allow the user to test ATevo to ensure it is operating correctly.
Screens permit the user to simulate alarm conditions, check set points and parameters,
exercise relays, and verify indicators are working as designed. Step-by-step guidance is
provided through the testing process. To start the Hindle Health System, press the Hindle
Health Button.
8.3.1 Introduction & Warning Screens
8.3.1 Introduction & Warning Screens
The first few health screens inform the user of how to navigate through the testing process and
how to track progress. The next screens warn about any hazardous conditions and identify any
tools required. To exit testing at any point, press ESC.
8.3.2 Test Selection
8.3.2 Test Selection
After the initial introduction and safety screens, a screen prompts the user to select the tests to
run.
There are two (2) test selections. The second will not test alarms or
relays:
• Operation, Set points, Alarms
• Operation, Set points
Copyright HindlePower Inc. 2021