14.1.4 Checking Temperature Compensation Probe – optional
14.1.4 Checking Temperature Compensation Probe – optional
If you are using the optional Temperature Compensation Probe (A10), confirm the probe is
securely installed. Make sure the connectors and the wiring from the probe to ATevo are in
satisfactory condition. If there is a failure of the temperature compensation probe, or the
wiring, ATevo will generate an alarm.
14.1.5 Measuring Output Ripple Voltage
14.1.5 Measuring Output Ripple Voltage
Measure ac ripple at the battery terminals at least once a year, using an rms responding ac
voltmeter. If the battery Ampere-hour capacity is at least four (4) times the output current
rating of ATevo, the ripple voltage should be no higher than the value featured in the
specifications in Appendix A.
Copyright HindlePower Inc. 2021
ATevo O&SI - 1PH Input Group I (6-25 Adc) - 1.1_en
Last modified: 2 August 2023
Page 270 of 316