Making Ac Input Connections - HindlePower ATevo Series Operating/Service Instructions Manual

Hide thumbs Also See for ATevo Series:
Table of Contents

Advertisement

HindlePower Inc
2.4.

2.4. Making AC Input Connections

Making AC Input Connections
ATevo is a commercial product. It is not intended for use at any time in a residential
environment or to be powered by low voltage public mains.
It is the responsibility of the installer to provide ac supply wiring approved for use in the
country where installed. When selecting wire sizes, consult the data nameplate decal affixed to
ATevo for voltage and current requirements.
GUIDELINES
GUIDELINES FOR
FOR SUPPLYING
1. Confirm that the ATevo nameplate voltage rating is correct for the ac input supply voltage.
If ATevo has the Multi-Tap ac input voltage option, make sure the setting matches the ac
input supply voltage (see
2. Use a branch circuit breaker or fused disconnect switch upstream from ATevo. This device
should have lockout capabilities so that the ac input supply to ATevo can be deenergized
for unit maintenance. A time-delay circuit breaker or slow-blow fuse is recommended.
3. Size the branch circuit breaker or fused disconnect switch for ATevo's maximum ac input
current as listed on the data nameplate decal. For a table of ratings, refer to standard
(JF5072-01).
4. Size the ac input wiring per the National Electric Code (NEC), Canadian Electrical Code,
local and site codes for the trip rating of the branch circuit breaker or fused disconnect
switch.
5. Conduit must be properly grounded, and in compliance with the national wiring rules of
the country where installed.
6. Do not run external ac input power wiring through the same conduit as external dc wiring.
7. Use copper or aluminum conductors only.
8. For 120 Vac, connect the neutral leg to input terminal (CB1-L2).
9. All site requirements of the facility take precedence over these instructions.
Copyright HindlePower Inc. 2021
SUPPLYING AC
AC POWER
Section 2.3.2, Verifying Multi-Tap AC Input Voltage
ATevo O&SI - 1PH Input Group I (6-25 Adc) - 1.1_en
POWER
Setting).