4.2.1.
4.2.1. How to Configure General
How to Configure General
Parameter Settings
Parameter Settings
You can adjust ATevo settings during operation using the front panel controls. When you first
press EDIT/ENTER on the front panel, ATevo prompts you to set the first of six (6) basic charger
parameters (Float Voltage).
To set parameters, do the following:
• Press UP or DOWN (or hold down to scroll) until desired value displays. Each parameter
has a minimum and maximum limit as listed in
• Press EDIT/ENTER to save setting. ATevo prompts you to set the next parameter.
• Continue in the same manner to set all six (6) parameters in the list. If you want to skip
setting any parameter, press EDIT/ENTER (or RIGHT arrow) to bypass it.
• When finished setting the sixth parameter (Current Limit), press EDIT/ENTER to save
setting and return to normal operation.
• Any changes made take effect immediately; ATevo uses its last saved values if it is
powered down and returned to service.
*
The Basic ATevo Set Point mode can also be entered from the Main Menu by
selecting the BASIC SETTINGS icon.
!
If you are interrupted while adjusting settings and do not press a front panel key
for 10 minutes, Edit Mode ends automatically without saving adjustments to any
setting not previously saved with the EDIT/ENTER key.