5.5. Disabling Ground Detection
Disabling Ground Detection
Depending on installation, users may wish to temporarily (or permanently) disable the ATevo
ground detect feature. If so:
1. Shut down ATevo, and allow internal voltages to dissipate.
2. Open the ATevo front panel door, and remove the safety shield.
3. Locate the Power Board (A2).
4. Identify the 3-pin shorting block (JP102), marked 'GROUND DETECT' on A2.
5. Move the 2-pin jumper from the ENABLED to DISABLED position.
6. Restart ATevo with ground detection disabled.