Contact Closure Programming

Testing Contact Closure Inputs

The Contact Closure Inputs may be manually toggled to allow for testing. Follow the procedure below to test the
Contact Closure Inputs. Note: The override function is only temporary. The actual CCI state will be restored
after leaving the Test CCI screen.
Step 1
Go to Contact Closure Setup
Main Menu
Contact Closure Setup
From Contact Closure Setup, select CCI 1 Setup,
CCI 2 Setup, or Security Setup.
Step 2
Enter Test Mode
CCI 2 Setup
Assign Zones
Set Zone Levels
Set Properties
Test CCI
Back
Use
and
to scroll down and select Test
CCI. Press "OK" to enter Test Mode.
Test CCI 2
CCI 2 State - Open
CCI 2 Scene - Off
Type - Maintained
Temporary Override - Off
Back
Override On
Press "Override On" (
the CCI states, or press "Back" (
to return to the previous menu.
Press "Back" (
the Contact Closure Setup menu to test
additional Contact Closure Inputs.
Note: The override function is only temporary.
The actual CCI state will be restored after
leaving the Test CCI screen.
Help
button) to toggle
button)
button) again to return to
Setup Guide for the RadioRA Chronos System Bridge