Contact Closure Wiring - Lutron Electronics seeTouch guestroom solutions Installation Manual

230 v 50/60 hz 8,75 a 40-350 w per zone, 24 v 200 ma panels with a power supply only
Table of Contents

Advertisement

Contact Closure Wiring

Contact Closure Ratings
Five Input Terminals
• Accepts maintained inputs and momentary inputs with 40 ms
minimum pulse times.
• Off-state leakage current must be less than 100 μA.
• Open circuit voltage: 24 V
• Inputs must be dry contact closure, solid state, open collector,
or active-low (NPN)/active high (PNP) output.
– O pen collector NPN or active-low on-state voltage must be
less than 2 V and sink 3,0 mA.
– O pen collector PNP or active-high on-state voltage must be
greater than 12 V and source 3,0 mA.
• Lutron recommends a maximum of 3 occupant sensors wired
in parallel per input.
Five Output Terminals
• Provide selectable maintained or momentary (250 ms) outputs.
• The interface is not rated to control unclamped, inductive loads.
Inductive loads include, but are not limited to, relays, solenoids,
and motors. To control these types of equipment, a flyback
diode must be used (DC voltages only). See diagram below.
• Output relays are non-latching (i.e. if relays are closed and
power is lost, relays will open).
IO Connections
1 2 3 4 5 6 7
LED 1: CCO 1
1 2 3 4 5 6 7
LED 2: CCO 2
LED 3: CCO 3
LED 4: CCO 4
LED 1: CCO 1
LED 5: CCO 5
LED 2: CCO 2
LED 6: Unused
LED 3: CCO 3
LED 7: Status
LED 4: CCO 4
LED 5: CCO 5
LED 6: Unused
LED 7: Status
Data Link (to wallstations)
1: Common
2: 24 V
Data Link (to wallstations)
3: MUX
1: Common
4: MUX
2: 24 V
3: MUX
4: MUX
10 seeTouch
guestroom solutions
®
maximum.
Program button
Program button
DIP switches
Notes: CCO LED is ON when CCO NO (normally
DIP switches
open contact) is closed.
Status LED blinks once per second
during normal operation
Notes: CCO LED is ON when CCO NO (normally
open contact) is closed.
Status LED blinks once per second
during normal operation
Contact Closure Outputs
Contact Closure Outputs
Contact
Closure
Inputs
NC = Normally closed
Contact
Closure
NO = Normally open
Inputs
NC = Normally closed
NO = Normally open
CCO and CCI connectors hold one
0,08 - 1,5 mm
(28 - 16 AWG) wire
2
CCO and CCI connectors hold one
0,08 - 1,5 mm
(28 - 16 AWG) wire
2
Output Ratings
Supply
Resistive
Voltage
Load
1,0 A
0 – 24 V
0,5 A
0 – 24 V
Flyback
Diode
(required for
Inductive
inductive
Load
loads)
NO
NC
IO
24 V
Output
COM
R
+
-
max.