PowPak
| Installation
TM
CCO Module
Part of the Energi TriPak
Family
TM
24 V~ 45 mA
RMJ-CCO1-24-B
NEC
24 V- 35 mA
Important Notes:
Please read before installing.
For installation by a qualified electrician in accordance with all local and
national electrical codes.
Note: Use copper conductors only.
Check to see that the device type and rating is suitable for the application.
DO NOT install if product has any visible damage.
If moisture or condensation is evident, allow the product to dry completely
before installation.
Operate between 32 °F (0 °C) and 131 °F (55 °C).
0% to 90% humidity, non-condensing.
For indoor use only.
PowPak
TM
CCO Module
Install in center of room to
maximize RF coverage.
Radio
Powr Savr
TM
Occupancy
Sensor
30 ft (10 m)
Maximum
Pico
®
Wireless
Transmitter
40 ft (12 m)
All Wireless Transmitters must be installed within
30 ft (10 m) of the PowPak
CCO Module.
TM
CCO Information
• This product features a single contact closure output with both
normally open (NO) and normally closed (NC) dry contacts.
• The CCO incorporates maintained output behavior only.
• The CCO is rated to switch resistive
Switching
Resistive
loads at voltages up to 24 V only. To
Voltage
Load
R
properly control inductive load types
0-24 V-
1.0 A
such as relays, solenoids, or motors,
0-24 V~
0.5 A
refer to Application Note #434.
Transmitting Device
Transmitted Command
CCO Default Action
Pico
On
NO = Close, NC = Open
®
Off
NO = Open, NC = Close
Raise
No Action
Lower
No Action
Preset
NO = Close, NC = Open
Radio Powr Savr
Occupied
NO = Close, NC = Open
TM
Occupancy Sensor
Unoccupied
NO = Open, NC = Close
Radio Powr Savr
Occupied
No Action
TM
Vacancy Sensor
Unoccupied
NO = Open, NC = Close
Radio Powr Savr
Ambient light below target level
NO = Close, NC = Open
TM
Daylight Sensor
Ambient light above target level
NO = Open, NC = Close
Lutron Electronics Co., Inc.
7200 Suter Road | Coopersburg, PA 18036-1299
Required Components
For each system ensure you have:
At Least One PowPak
CCO Module.
041-305
TM
Rev. A
08/2011
CLASS 2
®
CCO
CCO Toggle
Status
LED
Advanced
Operations
Contact
Closure
Output
(CCO)
(Class 2)
PowPak
CCO Module
TM
Start Here
1
Install PowPak
CCO Module
TM
When installing a PowPak
TM
Module, use the supplied mounting
screws and wire the module as shown.
Suggested Installation Location:
Install in center of room.
This ensures proper RF coverage of area.
Note: PowPak
CCO Module may also be
TM
mounted on or inside a junction box.
If installing unit inside a junction box please
see Application Note #423.
For more information:
www.lutron.com/powpakcco
2
Associate Wireless Transmitters to PowPak
Before beginning this step, make sure that there are no other PowPak
from other systems can be incorrectly associated to this system.
A
Permanently Install
3
Wireless Transmitters
Link
Test
Note: Please consult individual
component installation guides
for information.
Need Help? www.lutron.com or call the Lutron Technical Support Center, 24/7 at 1.800.523.9466
At least one Wireless Transmitter.
+
Radio Powr Savr
TM
Occupancy Sensor
(6 maximum)
Supply Voltage
CCO
24 V~ / 24 V-
Wire nut
(2 Supplied)
COM
(Common)
NC
NO
(Normally Closed)
(Normally Open)
CCO Module
TM
modules being set up within the same building. It is possible that Wireless Transmitters
TM
Hold the CCO Toggle
B
Hold the indicated button on a Wireless Transmitter for
button on the PowPak
6 seconds to associate the device.
TM
CCO Module for 6 seconds
Repeat for any additional Wireless Transmitters.
to enter association mode.
Note: The CCO will open and
Hold the CCO Toggle button on the PowPak
close once after each step to
C
confirm successful completion.
CCO Module for 6 seconds to save association(s).
Note: Only follow this step if using a Daylight Sensor with the CCO
4
Daylight Sensor Setup
Module to control a device that is switching a lighting source.
Calibration
A
Turn lights in room on using the
CCO Toggle button on the PowPak
Link
TM
CCO Module or an associated Pico
.
®
B
Press & hold "Cal." on the associated
Daylight Sensor for 6 seconds.
C
Exit room for 5 minutes to allow
calibration to be completed.
Link
Cal.
Test
Radio Powr Savr
Pico
Wireless
TM
®
Daylight Sensor
Transmitter
(1 maximum)
(9 maximum)
Note: CCO Module supply wires can be
connected in any polarity.
Mounting screw
(2 Supplied)
To CCO-controlled device.
Note: When wiring CCO output,
use 20 to 16 AWG (0.5 to 1.5 mm
)
2
solid or stranded wire.
Link
Test
TM
Tuning (Optional)
A
If it is desired to have multiple zones of
lights turn on at different daylight levels
Cal.
Test
(using multiple CCO Modules with one
Daylight Sensor) follow the Tuning
procedure described in the Daylight
Sensor's installation instructions (041-277).
Use the CCO Toggle button in place of the
Dimmer/Switch tap button referenced in
the document.
FCC Information:
This device complies with part 15 of the FCC Rules and Industry
Canada licence-exempt RSS standard(s). Operation is subject to
the following two conditions:
(1) This device may not cause interference, and
(2) this device must accept any interference, including
interference that may cause undesired operation.
Modifications not expressly approved by Lutron Electronics Co., Inc.
could void the user's authority to operate this equipment.
NOTE: This equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harm-
ful interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will
not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
Limited Warranty
(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)
Lutron will, at its option, repair or replace any unit that is defective in
materials or manufacture within one year after purchase. For warranty
service, return unit to place of purchase or mail to Lutron at 7200
Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.
This warranty is in lieu of all other express warranties, and the implied
warranty of merchantability is limited to one year from purchase. This
warranty does not cover the cost of installation, removal or reinstallation,
or damage resulting from misuse, abuse, or damage from improper
wiring or installation. This warranty does not cover incidental or
consequential damages.
LUTRON'S LIABILITY ON ANY CLAIM FOR DAMAGES ARISING
OUT OF OR IN CONNECTION WITH THE MANUFACTURE,
SALE, INSTALLATION, DELIVERY, OR USE OF THE UNIT SHALL
NEVER EXCEED THE PURCHASE PRICE OF THE UNIT.
This warranty gives you specific legal rights, and you may have other
rights which vary from state to state. Some states do not allow the
exclusion or limitation of incidental or consequential damages, or
limitation on how long an implied warranty may last, so the above
limitations may not apply to you. NEC is a registered trademark of
National Fire Protection Association, Quincy, Massachusetts. Lutron,
the Sunburst Logo, and Pico are registered trademarks and PowPak,
Radio Powr Savr and Energi TriPak are trademarks of Lutron
Electronics Co., Inc. ©2011 Lutron Electronics Co., Inc.
Reset Factory Defaults
Note: In some instances it may be necessary to reset the
PowPak
CCO Module back to factory default settings.
TM
A
Triple-tap the Advanced Operations button, "ADV"
on the PowPak
CCO Module and hold until the
TM
LED begins to flash slowly.
B
Within 3 seconds of flashing, release and triple-tap
the button again and the LED will flash rapidly
indicating that the unit has been reset to
factory defaults.
Note: Any associations or programming previously set
Cal.
up with the unit will be lost and will need to be
re-programmed.
Troubleshooting
www.lutron.com
CCO-controlled
• Ensure power to the PowPak
CCO
TM
device does
Module is properly applied.
not respond
• Ensure the CCO-controlled device has
to Wireless
been properly wired to the PowPak
TM
Transmitter(s).
CCO Module.
• Ensure Wireless Transmitter is properly
associated to PowPak
CCO Module.
TM
• Ensure Wireless Transmitter's battery is
installed correctly.
Wireless
• The maximum number of Wireless
Transmitters have been associated to
Transmitter(s)
the PowPak
CCO Module. To remove
cannot be
TM
a previously set up Wireless Transmitter,
associated to
tap the button used for association on
PowPak
TM
the Wireless Transmitter three times, on
CCO Module.
the third tap hold for three seconds
and then tap three more times.

Advertisement

loading

Summary of Contents for Lutron Electronics PowPak RMJ-CCO1-24-B

  • Page 1 CLASS 2 24 V- 35 mA ® interference that may cause undesired operation. CCO Toggle Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user’s authority to operate this equipment. Status Important Notes: Please read before installing.
  • Page 2 Radio Powr Savr et Energi TriPak sont des marques commerciales de Associez les transmetteurs sans fil au module CCO PowPak Lutron Electronics Co., Inc. ©2011 Lutron Electronics Co., Inc. Réinitialisez les réglages par Avant de commencer cette étape, veillez à ce qu’il n’y ait pas d’autres modules PowPak en cours d’installation à...