Compliance With Rules In Force; En50131, Grade 2 - INIM Electronics Prime Programming Manual

Anti-intrusion control panels and security systems
Table of Contents

Advertisement

19
Chapter
NBY/X
ANTI-
DISLODGEMENT OF
CONTROL PANEL
KEYPADS
FLEX5/U
ZONE BALANCING
TAMPER EVENTS
PIN
TIMERS
19-1
OPTIONS
Parameter
Wrong PIN keypad lockout Table 3-1: Parameters
Does not arm if any of the
zones are not ready
Prevents the deletion of
tamper memory by user
code
78

Compliance with rules in force

In order to guarantee compliance with the regulations in force, you must adhere to the
following guidelines:
The nBy/X readers must be equipped with devices that protect them against the forced-
opening of their casings (EN50131 grade 2) and dislodgement from their placements
(EN50131 grade 3), as indicated in paragraph 3-2-10 Installing nBy/X readers in the
Installation manual.
The protection against control panel tamper (Table 4-3: Control panel options) must be
enabled (EN50131 grade 3).
JOY, Aria/HG, nCode and Concept keypads must be equipped with enabled tamper-protection
devices, as indicated in paragraph 3-3-2 Addressing the keypads in the Installation manual.
The FLEX5/U devices must be mounted inside the enclosure of Prime control panels (refer to
the Installation manual, Table 2-5: Control panels - description of parts, M), or must be
equipped with a device that protects them against the forced-opening of their casings
(EN50131 grade 2) and dislodgement from their placements (EN50131 grade 3).
The lines relating to the intrusion-detection zones must be configured as 'Double balancing'
with double EOL resistors, or as Single balancing with single EOL resistor. They must also be
equipped with devices which protect them against the forced-opening of their casings.
Terminal tamper, peripheral tamper and control-panel tamper events must trigger audible
signals (sounder signals) for a period of not less than 3 minutes.
The output activated by the previously mentioned tamper events must be different from the
output activated by alarms signals.
All Code PINs must have 6 digits.
If a Timer is used for automatic-arming operations, the Pre-arm times must be programmed
separately for each partition (the pre-arm time must not be set at "0").

EN50131, Grade 2

Compliance with EN50131 Grade 2 is guaranteed by observing the following guidelines.
Table 19-1: EN50131 grade 2 - Enablement of options
common to all keypads
Table 4-3: Control panel
options
Software section
Installer menu section
Keypad parameters
Parameters,
Control panel
parameters
Centrali anti-intrusione
Status
Enabled
Keypad lockout
Enabled
OpenZonesArmLock
Enabled
NoUserTamp.reset
Compliance with rules in force