Programming manual
• Zone status - allows you to view the status of all the zones. Use keys
scroll the list of accessible zones. The display shows the following zone parameters:
Table 18-2: View Nexus status on the keypad
Line
Display
1
FD living room
2
Standby Unbypsed
3
Lev.07 000 mdB/m
4
Dust level 000%
It is advisable to clean the detector when the value exceeds 90%.
• Faults ongoing - allows you to view any ongoing faults.
• Panel version - allows you to view the firmware version and model of the Prime control
panel.
Allows manual activation/deactivation of the outputs by means of keys
Allows you to set the date and time of the control panel (refer to paragraph 4-2 Prime control
panel).
The Prime/STUDIO software program provides a section which, during a direct connection to a
Prime control panel, allows you to monitor the entire system in real time and access some of
the above-mentioned parameters.
Select the "Monitoring" option from the menu bar.
A window containing various sections will open. The sections can be selected by means of
tags, each referring to a different part of the system (refer to Chapter 21 Monitoring the
control panel).
User functions for the installer
Zone description
Zone status ("Standby", "Alarm", "Short", "Tamper"), its
activation status ("unbypassed" - capable of generating
alarms, or "bypassed" - incapable of generating alarms)
Various indications depending on the device type:
wired zone; resistance value reading expressed Ohm
wireless zone; wireless signal reception level (from 0 to 7)
Air2-FD100 smoke detector, strength of wireless signal and
level of smoke present in the smoke detection chamber,
expressed in mdB/m
Level of contamination present in the smoke detection
chamber of the Air2-FD100 smoke detector (%)
and
View
and
.
to
Note
OUTPUTS ON/OFF
WRITE DATE/TIME
Via software