Goodrive300-01A series VFD for air compressor
Function
Name
code
Frequency drop at
P11.01
transient power dip
Frequency drop rate at
P11.02
transient power dip
Overvoltage stall
P11.03
protection
Overvoltage stall
P11.04
protection voltage
P11.05
Current limit selection
Automatic current-limit
P11.06
Frequency drop rate at
P11.07
current limit
1: Enable input phase loss software protection
Note: LED ones place detects input phase
loss by phase sequence detection circuit.
LED tens:
0: Disable output phase loss protection
1: Enable output phase loss protection
LED hundreds:
0:
Disable
protection
1:
Enable
protection
Note: LED hundreds place detects input
phase loss by hardware detection circuit.
LED thousands:
0: Disable phase sequence protection
1: Enable phase sequence protection
0: Disable
1: Enable
0.00Hz–P00.03/s (max. frequency)
0: Disable
1: Enable
120–150% (standard bus voltage) (380V)
0x00–0x11
Ones: Current-limit action selection
0: Current-limit action is invalid
1: Current-limit action is always valid
Tens: Hardware current-limit overload alarm
selection
0: Hardware current-limit overload alarm is
valid
1: Hardware current-limit overload alarm is
invalid
50.0–200.0%
level
0.00–50.00Hz/s
Description
input
phase
loss
input
phase
loss
-58-
Function code description
Default Modify
hardware
hardware
0
10.00Hz/
s
1
140%
01
160.0%
10.00Hz/
s
○
○
○
○
◎
◎
◎