8-port io-link master class a; ethernet/ip; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

765-4501/0100-0000
IO-Link Port
1
2
3
...
The following table describes the attributes of instances 100, 101 etc.
At-
tribute
2
9
10
11
12
13
14
19
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
Name
n/a
Access Data Type Description
State
V
Get
Logged Data
n/a
Get, Set BYTE
Configuration
Log Full Action n/a
Get, Set USINT
Duplicate
n/a
Get, Set USINT
Event Action
Event/Data
V
Get
Log Maximum
Size
Event/Data
V
Get
Log Size
Event/Data
V
Get
Log
Get
Member
Remove
Member
Log Full
V
Get
Table 89: Mapping CIP Instances to IO-Link Ports
CIP Instance
100
101
102
...
Table 90: Instance Attributes of Event Log Object 65 (0x41)
USINT
Status of this instance 0: does not exist
1: stopped
2: empty
3: present
4: full/overwrite
5: full/stop
6–255: reserved
Determines what data is saved in the event
log.
Bit 0 = 0: log event without time value
Bit 0 = 1: log event with time value
Bits 1–7: reserved (always 0)
Determines what to do when a new event
is detected and the log is full.
0: stop
1: scroll
2–255: reserved
Determines what to do if a duplicate event
is detected.
0: ignore
1: add
2–255: reserved
UDINT
Max. number of entries in the event log.
UDINT
The current number of entries in the event
log.
Values: 0 to maximum (= value of attribute
12).
ARRAY
List of all logged events.
of
An entry contains the IO-Link event quali-
STRUCT
fier (USINT) and the IO-Link event code
(UINT). Attribute 9 determines whether a
timestamp (STIME) is stored in addition.
The structure of an entry is described be-
low.
BOOL
Log full?
False: log is not full
True: log is full
Diagnostics
Default
-
0
1
1
8
0
0
False
121