10.2.1.3 Setting Parameters

Set the module and port parameters in the configuration software of the EtherNet/IP
scanner to define the behavior of the module and the required port functions for use of
the connected sensors and actuators.
You can find all the module parameters under

10.3 Parameterization

The following tools are described below:

• WAGO Webserver I/O Field

8 WAGO IO-Link Configurator [} 111]
• WAGO I/O Field app
• OPC UA Server
10.3.1 WAGO Webserver I/O Field

10.3.1.1 Call WAGO Webserver I/O Field

This section describes how you can use the integrated software "WAGO Webserver I/O
Field" to get access to detailed information on the current operating state of the product
and make settings to affect the product's behavior.
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
Name
Description
Exclusive Owner –
No port parameters are transferred to the module through this
16 bytes per IO-Link
connection.
port without config
The scanner can read the module's input data and write the
output data.
IO-Link devices with up to 16 IO-Link input and output data
points each can be used.
Listen Only –
No port parameters are transferred to the module through this
16 bytes per IO-Link
connection.
port
The scanner can read the module's input data.
An additional scanner that communicates with module via an
"Exclusive Owner" connection is necessary.
IO-Link devices with up to 16 IO-Link input and output data
points each can be used.
Input Only – 16
The port parameters are set with the configuration software of
 bytes per IO-Link
the scanner and transferred to the module through this con-
port
nection.
The scanner can read the module's input data.
IO-Link devices with up to 16 IO-Link input and output data
points each can be used.
Exclusive Owner –
Like connection 5, but IO-Link devices with at most 4 IO-Link input
4 bytes per IO-Link
and output data points.
port
Exclusive Owner –
Like connection 6, but IO-Link devices with at most 4 IO-Link input
4 bytes per IO-Link
and output data points.
port without config
Listen Only – 4 bytes
Like connection 7, but IO-Link devices with at most 4 IO-Link input
per IO-Link port
and output data points.
Input Only – 4 bytes
Like connection 8, but IO-Link devices with at most 4 IO-Link input
per IO-Link port
and output data points.
8 Module Parameters
[} 63].
Commissioning