WAGO TEchDocs 765-4501/0100-0000 Manual page 124

8-port io-link master class a; ethernet/ip; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

Diagnostics
Event Code
0x180D
0x180E
0x180F
0x1810
0x1811
0x1812
0x1813
IO-Link Device Event Codes (General)
The following table lists standard IO-Link-Device event codes. For device-specific event
codes or corrective action, consult the manual of the IO-Link device used.
Event Code
0x0000
0x1000
0x1800 –
0x18FF
0x4000
0x4210
0x4220
0x5000
0x5010
0x5011
0x5012
0x5013
0x5100
0x5101
0x5110
0x5111
0x5112
0x6000
0x6320
0x6321
0x6350
0x7700
0x7701 –
0x770F
0x7710
0x7711
0x8C00
0x8C01
124
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
Description
Parameter inconsistency: download
error
Class B: undervoltage on pin 2 (2L+
power supply)
Class B: short circuit on pin 2 (2L+
power supply)
Short circuit on pin 2 (DIO)
Short circuit on pin 4 (DIO)
Overcurrent on pin 2 (DIO)
Overcurrent on pin 4 (DIO)
Description
No malfunction
General malfunction (unknown error)
Manufacturer-specific
Temperature error – overload
IO-Link device: overtemperature
IO-Link device: undertemperature
IO-Link device: hardware error
Component: malfunction
Loss of non-volatile memory
Batteries weak
HMI button pressed
General power supply error
Fuse blown/open
Primary power supply: overvoltage
Primary power supply: undervoltage
Secondary supply voltage: error (port
class B)
IO-Link device: software error
Parameter error
Parameter missing
Parameters modified
Lower-level IO device: wire break
Lower-level IO device 1 ... 15: wire
break
Short circuit
Reference potential: error
Technology-specific application error
Simulation active
Type
Corrective Action
Error
Check IO-Link device, check connec-
tion to IO-Link master
Error
Check power supply
Error
Check installation and load
Error
Check installation and load
Error
Check installation and load
Error
Check load and installation
Error
Check load and installation
Table 95: IO-Link Device Event Codes (General)
Type
Corrective Action
Notification
No need for action
Error
See the manual of the IO-Link device
used
See the manual of the IO-Link device
used
Error
Check temperature, determine cause
of overload
Warning
Eliminate cause of heat
Warning
Insulate IO-Link device
Error
Replace IO-Link device
Error
Repair or replace
Error
Check batteries
Warning
Replace batteries
Notification
-
Error
Check power supply
Error
Replace fuse
Warning
Check the tolerance of the 1L+ volt-
age
Warning
Check the tolerance of the 1L+ volt-
age
Warning
Check the tolerance of the 2L+ volt-
age
Error
Check firmware version
Error
Check data sheet and values
Error
Use data sheet for check
Error
Check configuration
Error
Check installation
Error
Check installation
Error
Check installation
Error
Check installation
Error
Reset IO-Link device
Warning
Check operating mode
765-4501/0100-0000

Advertisement

Table of Contents
loading

Table of Contents