9.4 Connecting the Fieldbus

To establish a connection to an EtherNet/IP scanner, it is necessary to connect the mod-
ule to an ETHERNET network.
To establish a connection to an IO controller, connect the product to a network with a
transmission rate of 100 Mbit/s in full duplex operation.
You can find the connection assignment for the ETHERNET ports under
Interfaces
If you do not use a pre-assembled ETHERNET cable, a shielded M12 plug with protec-
tion type IP 67 should be connected to it.
For a cable that is pre-assembled on one end only (e.g., item no. 756-1201/0060-xxxx),
proceed as follows to connect it to an RJ45 plug (e.g., item no. 750-0975):
Because the Auto MDI(X) functionality is enabled for the respective ETHERNET connec-
tion, a crossover cable is not necessary. This functionality automatically detects the direc-
tion for sending data and receiving data, so it is irrelevant which cable type is used
(crossed or uncrossed).
Connecting an Individual Product to an ETHERNET Network
To connect the product to the ETHERNET network, proceed as follows:
1. Disconnect the power supply from the equipment parts on which you have mounted
the module.
2. Connect the product to the ETHERNET network by plugging the socket of the ETH-
ERNET cable onto the X21 connection.
3. Tighten the pluggable connector using the knurled-head screw.
Connecting Multiple Products to One ETHERNET Network
The fieldbus module of the WAGO I/O System Field has two connections with an inte-
grated switch to allow wiring of a line topology.
The network topology in the following figure consists of a mixed star and line topology. An
ETHERNET switch is required in order to set up a star topology or a mixed topology. The
number of products in a star topology is limited only by the IEEE 802.3 Ethernet specifi-
cation.
Multiple products can be connected to the ETHERNET network as shown in the following
example:
1. De-energize the section of your system to which you wish to mount the product.
2. For the star topology, connect each ETHERNET cable (W1, W2) to port X21 of one
765 Series product and one ETHERNET switch as shown in the following figure.
Then tighten the plugs of the ETHERNET cable.
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
[} 18].
Connection
8 ETHERNET
Figure 8: RJ45 Pin Assignment