Forcing; Table 37 Port Qualifier Information - WAGO TEchDocs 765-4501/0100-0000 Manual

8-port io-link master class a; ethernet/ip; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

765-4501/0100-0000
Byte Off-
set
Output Process Data of Connections 11 and 12
Connections 11 and 12 have no output process data.
Port Qualifier Information
The PQI (Port Qualifier Information) provides status information for the IO-Link port and
the IO-Link device.
Bit
0
1
2
3
4
5
6
7

5.2 Forcing

This section describes the "Force" function for the module's input and output data.
In forcing, the physical states of the inputs or the output values of the higher-level con-
troller are "forcibly" overwritten with other values. The user provides these values and
identifies them as forcing values. This method is helpful for commissioning systems and
troubleshooting.
The "Forcing" function can be accessed through the following tools:
• WAGO I/O Field Webserver
• WAGO I/O Field app on mobile devices
Systems like SPS, TIA Portal and the like also have forcing functions. Such forcing func-
tions should not be confused with the ones described in this section and will not be con-
sidered within the context of this section.
A distinction is made between two types of forcing:
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
Bit
Output Process Data
6
Port X07, pin 2: DO B
7
Port X08, pin 2: DO B
Flag
Description
Reserved, 0
Reserved, 0
Reserved, 0
Event
IO-Link event
The value corresponds to attribute 20 of event log object 65 (0x41).
0: The port has no IO-Link event.
1: The port has an IO-Link event. The event can be read out via event log object 65
(0x41).
Reserved, 0
DevCom
IO-Link device communication
0: No IO-Link device present
1: IO-Link device detected in state PREOPERATE or OPERATE
DevErr
Port/device error
0: No error/warning occurred
1: Error/warning occurred on port or IO-Link device
PQ
Validity of the device process data
0: Invalid I/O process data from IO-Link device
1: Valid I/O process data from IO-Link device
Functions
Table 37: Port Qualifier Information