Selection Option
Digital input, normally
closed
Digital Output
Digital output, static on
Configuring the Device Check for Validation and Backup
Note
In the "IOL Autostart" operating mode (see above), this drop-down menu has no ef-
fect.
The Validation and backup drop-down menu can be used to determine whether a vali-
dation (device check) is performed and, if so, at what level (Inspection Level) when a con-
nected device is replaced, and whether or not the stored operating parameters of the old
device are carried over to the new one.
The following table explains the possible values for Inspection Level:
Inspection Level
NO_CHECK
TYPE_COMP
IDENTICAL
The Backup Level parameter determines the system behavior when a device connected
to the port is replaced in terms of continued operation with unmodified device parameters.
This parameter can have three different values:
Backup Level
Commissioning
("Disable")
Production
("Backup/Restore")
Production
("Restore")
The Validation and Backup drop-down menu offers the following options for setting the
Inspection Level and Backup Level parameters:
94
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
Explanation
Pin 2 is a digital input. The signal is inverted.
Pin 2 is a digital output.
Pin 2 is a digital output. The signal is permanently set to logic 1 (for testing pur-
poses only).
Table 61: Possible Values of the Inspection Level Parameter
Description
No device check is performed.
A device check for type compatibility is performed.
For the device check, the actual vendor ID is compared to the vendor ID setting in
the configuration, and the actual device ID is compared to the device ID setting in
the configuration.
A device check for device identity is performed.
For this purpose, a device check for type compatibility is performed. Furthermore,
the actual serial number is compared to the serial number setting of the configura-
tion.
Table 62: Possible Values of the Backup Level Parameter
Description
Parameter data of the old device is not saved for transfer to the new device. There-
fore, if the device is replaced, the new device must be parameterized anew.
Changes to all active parameters within the device are copied and saved. Thus all
parameter data of the old device is stored for transfer to a new device.
Device replacement with automatic or semi-automatic data storage is supported.
Changes to all active parameters within the device are not copied and saved. Only
special parameter data of the old device is stored for transfer to a new device.
Device replacement with automatic or semi-automatic data storage is only sup-
ported for these "frozen" parameters.