Commissioning

10.3.1.4.1 Configure Ports

The Configuration tab is used to display and modify the following port settings for the se-
lected port of the device:
Name
Port mode (pin 4)
Digital input signal filter
(pin 4)
IQ behavior (pin 2)
Validation and backup
PortCycleTime
VendorID
DeviceID
The Validation and Backup, PortCycleTime, VendorID and DeviceID settings only ap-
pear for the IOL Manual selection in the Port mode (pin 4) drop-down menu.
Changes to settings require operator or admin rights. If you do not have these, the Con-
figuration tab is grayed out, and the displayed values cannot be edited.
If cyclic data exchange takes place via PROFINET, no configuration is possible. In this
case, a message appears:
Note: Changing configuration not allowed because interface state
is "communicating."
To makes changes to a port's configuration, proceed as follows:
1. Select the desired port (port X01, port X02 etc.) from the menu
2. Open the Configuration tab.
3. Configure pin 4 by setting the port operating mode.
92
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
Table 58: Port Configuration Settings for IO-Link Devices
Type
Description
Drop-down menu
Port operating mode (configuration of pin 4)
Drop-down menu
Filter time for digital input signals on pin 4 (only for
"Port mode (pin 4)" on digital input)
Drop-down menu
IQ behavior of the port (configuration of pin 2)
Drop-down menu
Validation and Backup Settings for Device Check
When Replacing Devices
Input field
Expected cycle time of the port
Input field
Expected manufacturer ID of the connected device
Input field
Expected device ID of the connected device
765-4501/0100-0000
Figure 16: Port XX Menu Item, Configuration Tab