10.3.1.3.6 Revision ID

This shows the version ID of the connected device.
A value of 0 means: no device connected.
All other values must be interpreted as the version ID of the connected device.

10.3.1.3.7 Baud Rate

If an IO-Link device is connected to the port, its data transmission rate appears here. For
IO-Link, the transmission rate of the communication between the port and a connected
device can have the following values:
• 4.8 kbit/s (COM1)
• 38.4 kbit/s (COM2)
• 230.4 kbit/s (COM3)
If no IO-Link device is connected to the port, the text Not connected appears here.

10.3.1.3.8 Cycle Time

The cycle time of the master is bit-coded as follows:
• Bits 0 ... 5 specify a whole-number multiplier between 0 and 63.
• Bits 6 ... 7 specify the calculation formula to use according to the following table:
Bits 6 ... 7
0
1
2
3

10.3.1.3.9 Input Data Length

This shows the actual input data length of the connected product in bytes.

10.3.1.3.10 Vendor ID

This value is the manufacturer ID of the connected product.

10.3.1.3.11 Device ID

This value is the device ID of the connected product.

10.3.1.3.12 Displaying Process Data

You can view the process data associated with a specific port on the Process Data tab.
Proceed as follows to view the process data for a port:
1. From the main menu of the Webserver (left), select the menu item which you want to
view information about.
2. Open the Process Data tab.
90
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
Table 57: Cycle Time of the Master – Bits 6 ... 7
Calculation Formula
Multiplier × 0.1 ms
6.4 ms + multiplier × 0.4 ms
32.0 ms + multiplier × 1.6 ms
Reserved