Diagnostics Via Ethernet/Ip - WAGO TEchDocs 765-4501/0100-0000 Manual

8-port io-link master class a; ethernet/ip; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

Diagnostics
IO-Link Port Status
LEDs 0 (port X01), 2 (port X02), 4 (port X03), ..., 14 (port X08) indicate the status of the
IO-Link Master or digital input/output channel A.
LEDs 1 (port X01), 3 (port X02), 5 (port X03), ..., 15 (port X08) indicate the status of the
digital input/output channel B.
LED
0, 2, 4, ...
IO-Link Port Chan-
nel A
(pin 4)
1, 3, 5, ...
IO-Link Port Chan-
nel A
(pin 2)

11.2 Diagnostics via EtherNet/IP

The module contains the event log object with information on IO-Link events. The con-
troller can read the attributes of the event log object in order to get the "Event Qualifier"
and "Event Code" of an IO-Link event. A CIP instance is assigned to each IO-Link port.
Event Log Object 65 (0x41)
• Instance 0 (class attribute):
The event log object contains information on IO-Link events.
At-
tribute
1
0
32
33
• Instances 100, 101, ... (instance attribute):
The following table shows the assignment of CIP instances to IO-Link ports.
120
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
Color
Duo LED, yellow/red/green (yellow = simultaneously red and green)
yellow
Off
green
green
red
red
Duo LED, yellow/red (yellow = simultaneously red and green)
yellow
Off
red
red
Name
n/a
Access Data Type Description
Version
n/a
Get
Max. instance n/a
Get
Time format
n/a
Get
Present time
n/a
Get
State
Description
On
Status of digital input/output channel A: 1
Off
Status of digital input/output channel A: 0
On
IO-Link communication active
Flashing 1 Hz
No IO-Link communication or incorrect IO-
Link device
On
Overload, short circuit (pin 4 and pin 3)
Flashing 1 Hz
Overload, sensor supply short circuit (pin 1
and pin 3)
On
Status of digital input/output channel B: 1
Off
Status of digital input/output channel B: 0
On
Overload, short circuit (pin 2 and pin 3)
Flashing 1 Hz
Overload, sensor supply short circuit (pin 1
and pin 3)
Table 88: Event Log Object 65 (0x41) Class Attributes
UINT
Version of this object
UINT
Number of IO-Link ports
USINT
Data type identifier of the time format
Only the STIME data type is supported.
USINT
Default for time value
Applies to all instances.
765-4501/0100-0000
Table 87: IO-Link Port Status (Class A)
Default
1
1 – 8
204 (0xCC)
= STIME
0

Advertisement

Table of Contents
loading