Diagnostics
EtherNet/IP Adapter Status
The MS and NS LEDs indicate the status of the EtherNet/IP module.
The LNK and ACT LEDs indicate the Ethernet status.
LED
MS
(module status)
NS
(Network status)
118
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
Color
State
Duo LED, red/green
Green
On
Green
Flashing (1 Hz)
Green/red/green
Rapid flashing:
green/red/green
Red/green/off
Flashing sequence:
red/green/off
Red
Flashing (1 Hz)
Red
On
Off
Off
Duo LED, red/green
Green
On
Green
Flashing (1 Hz)
Green/red/off
Rapid flashing:
green/red/off
Red/green/off
Flashing sequence:
red/green/off
765-4501/0100-0000
Table 82: Status of the EtherNet/IP module
Description
Module in operation: The module is in op-
eration and working correctly.
Standby: The module has not been config-
ured.
Self test: The module runs through a self
test after it is switched on. The following se-
quence occurs during the self test:
NS LED off
MS LED lights up green for about
250 ms, turns red for about 250 ms and
then lights up green again (and contin-
ues to do so until the test is completed).
NS LED lights up green for about
250 ms, turns red for about 250 ms and
then goes out (and remains off until the
test is completed).
Flashing sequence: The flashing se-
quence identifies the adapter visually. The
scanner can start the flashing sequence in
identity object 1 of the adapter. The MS
LED and NS LED go through the flashing
sequence simultaneously.
Serious recoverable error: The module
has identified an error that is serious but
can be fixed – for example, an incorrect or
inconsistent configuration may be classified
as a serious recoverable error.
Serious unrecoverable error: The module
has identified an error that is serious and
cannot be fixed.
Switched off: The module is switched off.
Connected: An IP address is configured, at
least one CIP connection (of any transport
class) has been established, and, for an
Exclusive Owner connection, the time limit
has not been exceeded.
No connection: An IP address has been
configured, but no CIP connections have
been established, and, for an Exclusive
Owner connection, the time limit has not
been exceeded.
Self test: The module runs through a self
test after it is switched on. See the descrip-
tion of the "MS" LED and the description of
the "Self test" status.
Flashing sequence: The flashing se-
quence identifies the adapter visually. The
scanner can start the flashing sequence in