WAGO TEchDocs 765-4501/0100-0000 Manual page 123

8-port io-link master class a; ethernet/ip; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

765-4501/0100-0000
Bit
Bits 6–7
Bits 4–5
Bit 3
Bits 0–2
IO-Link Master Event Codes
Event Code
0x0000
0x1800
0x1801
0x1802
0x1803
0x1804
0x1805
0x1806
0x1807
0x1808
0x1809
0x180A
0x180B
0x180C
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
Name
Mode
Type
Source
Instance
Description
No malfunction
No IO-Link device (communication);
communication with IO-Link device
lost
Startup parameterization error
Discrepancy during validation: incor-
rect VendorID
Discrepancy during validation: incor-
rect DeviceID
Short circuit on pin C/Q (pin 4)
Overtemperature (on the port)
Short circuit on pin 1 (1L+ power sup-
ply)
Overcurrent on pin 1 (1L+ power sup-
ply)
IO-Link device event overrun
Backup inconsistency: insufficient
memory (2048 octets)
Backup inconsistency: identity error
Backup inconsistency: data storage,
unspecified error
Backup inconsistency: upload error
Description
0: reserved
1: single event
2: event disappears
3: event appears
0: reserved
1: notification
2: warning
3: error
0: device (remote)
1: master/port
0: unknown
1–3: reserved
4: application
5–7: reserved
Table 94: IO-Link Master Event Codes
Type
Corrective Action
Notification
No need for action
Error
Check of whether IO-Link device is
connected
Error
Check parameters
Error
Use correct IO-Link device type
Error
Use correct IO-Link device type
Error
Check installation
Error
Check temperature and load
Error
Check installation
Error
Check power supply
Error
Check IO-Link device
Error
Delete data storage by reconfiguring
the port
Error
Delete data storage by reconfiguring
the port
Error
Delete data storage by reconfiguring
the port
Error
Check IO-Link master, check connec-
tion to IO-Link device
Diagnostics
Figure 30: Event qualifier
Table 93: Event Qualifier
123

Advertisement

Table of Contents