Reading Process Data; Reading Out Measured Values; Table 72 Port-Specific Configuration Parameters - WAGO TEchDocs 765-4501/0100-0000 Manual

8-port io-link master class a; ethernet/ip; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

Commissioning
The following table lists port-specific configuration parameters.
Node Name
OverCurrentPin1, Over-
CurrentPin2, OverCur-
rentPin4
UnderCurrentPin1, Un-
derCurrentPin2, Under-
CurrentPin4

10.3.4.1.3 Reading Process Data

The OPC UA server provides nodes with process data. For example, the OPC UA client
can read out the value on pin 2 of a port in the Pin2ProcessData node. The path to this
node is:
Root > Object > DeviceSet > [device name] > IOLinkMaster > PortXX
> ProcessData
Note
OPC UA client can only read process output data
The process output data is written by the EtherNet/IP scanner. The OPC UA client can
only read process output data.
The following table lists port-specific process data.
Node Name
Pin2ProcessData
Pin4ProcessData

10.3.4.1.4 Reading out Measured Values

The OPC UA server provides nodes with calculated measured values. For example, the
OPC UA client can read out the calculated total current of supply cable 1 in the SumCur-
rentL node. The path to this node is:
Root > Object > DeviceSet > [device name] > IOLinkMaster > Diag-
nostics > Current
The following table lists device-specific (calculated) measured values.
Node Name
SumCurrentL
SumCurrentL2
MeanTemperature
114
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
Node Class
Access Default Description
Variable
Read
0
Variable
Read
0
Node Class
Access
Variable
Read
Variable
Read
Node Class
Access
Variable
Read
Variable
Read
Variable
Read
Table 72: Port-Specific Configuration Parameters
Warning level for current upper limit on pin 1, pin
2 or pin 4; unit: 1 mA
0: monitoring not enabled
Warning level for current lower limit on pin 1, pin
2 or pin 4; unit: 1 mA
0: monitoring not enabled
Table 73: Port-Specific Process Data
Description
Process data on pin 2
Process data on pin 4
Table 74: Device-Specific (Calculated) Measured Values
Description
Total current in supply cable 1 calculated
from individual measurements; unit: mA
Total current in supply cable 2 calculated
from individual measurements; unit: mA
Average value for the temperature of the
assembly, calculated from the temperature
values measured individually on the three
chips; unit: °C
765-4501/0100-0000