Danfoss VLT HVAC Basic Drive FC 101 Programming Manual

Danfoss VLT HVAC Basic Drive FC 101 Programming Manual

Hide thumbs Also See for VLT HVAC Basic Drive FC 101:
Table of Contents

Advertisement

MAKING MODERN LIVING POSSIBLE
Programming Guide
®
VLT
HVAC Basic Drive FC 101
www.danfoss.com/drives

Advertisement

Table of Contents
loading

Summary of Contents for Danfoss VLT HVAC Basic Drive FC 101

  • Page 1 MAKING MODERN LIVING POSSIBLE Programming Guide ® HVAC Basic Drive FC 101 www.danfoss.com/drives...
  • Page 3: Table Of Contents

    ® Contents HVAC Basic Drive FC 101 Programming Guide Contents 1 Introduction 1.1 Purpose of the Manual 1.2 Document and Software Version 1.3 Safety Symbols 1.4 Safety Precautions 1.5 Additional Resources 1.6 Definitions 1.7 Electrical Overview 2 How to Programme 2.1 Programming with MCT 10 Setup Software 2.2 Local Control Panel (LCP) 2.3 Menus...
  • Page 4 ® Contents HVAC Basic Drive FC 101 Programming Guide 4.1 Alarms and Warnings 4.2 Alarm Words 4.3 Warning Words 4.4 Extended Status Words 4.5 List of Warnings and Alarms 5 Parameter Lists 5.1 Parameter Options 5.1.1 Default Settings 5.1.2 0-** Operation/Display 5.1.3 1-** Load and Motor 5.1.4 2-** Brakes 5.1.5 3-** Reference/Ramps...
  • Page 5: Introduction

    Introduction ® HVAC Basic Drive FC 101 Programming Guide 1 Introduction 1.1 Purpose of the Manual 1.4 Safety Precautions WARNING This programming guide provides information for advanced programming of the frequency converter. It The voltage of the frequency converter is dangerous provides a complete overview of all parameters as well as whenever connected to mains.
  • Page 6: Additional Resources

    A motor that has been stopped with the mains • VLT HVAC Basic Drive FC 101 Design Guide entails supply connected, may start if faults occur in the all technical information about the frequency electronics of the frequency converter, through converter and customer design and applications.
  • Page 7 Introduction ® HVAC Basic Drive FC 101 Programming Guide Motor References Analog reference The motor frequency when the jog function is activated A signal transmitted to the analog inputs 53 or 54, can be voltage or current. (via digital terminals). Bus reference The motor frequency.
  • Page 8 Introduction ® HVAC Basic Drive FC 101 Programming Guide Intermittent duty cycle Smart Logic Control (SLC) An intermittent duty rating refers to a sequence of duty The SLC is a sequence of user defined actions executed cycles. Each cycle consists of an on-load and an off-load when the associated user defined events are evaluated as period.
  • Page 9: Electrical Overview

    Introduction ® HVAC Basic Drive FC 101 Programming Guide 1.7 Electrical Overview 3 Phase power input Motor UDC- Not present on all power sizes UDC+ 50 (+10 V OUT) relay2 +10 V DC 240 V AC 3 A 0-10 V DC- 53 (A IN) 0/4-20 mA 54 (A IN)
  • Page 10: How To Programme

    (set-up 12). The number flashing, indicates the This software can either be ordered using code number edit set-up. 130B1000 or downloaded from www.danfoss.com/Busines- Motor direction is shown to the bottom left of the display sAreas/DrivesSolutions/softwaredownload. – indicated by a small arrow pointing either clockwise or counterclockwise.
  • Page 11: Menus

    How to Programme ® HVAC Basic Drive FC 101 Programming Guide 2.3.3 Start-up Wizard for Open Loop Applications 2.3 Menus 2.3.1 Status Menu The built-in wizard menu guides the installer through the set up of the frequency converter to an open loop application.
  • Page 12 How to Programme ® HVAC Basic Drive FC 101 Programming Guide ... the HVAC FC 101 Wizard starts Select Regional Settings At power up the user is Power kW/50 Hz asked to choose the Setup 1 prefered laguage. Grid Type 200-240V/50Hz/Delta Setup 1 Select language...
  • Page 13 How to Programme ® HVAC Basic Drive FC 101 Programming Guide Start-up Wizard for Open Loop Applications Parameter Range Default Function 0-03 Regional Settings [0] International [1] US 0-06 GridType [0] 200-240 V/50 Hz/IT-grid Size related Select operating mode for restart upon [1] 200-240 V/50 Hz/Delta reconnection of the frequency converter to mains [2] 200-240 V/50 Hz...
  • Page 14 How to Programme ® HVAC Basic Drive FC 101 Programming Guide Parameter Range Default Function 1-24 Motor Current 0.01-10000.00 A Size related Enter motor current from nameplate data 1-25 Motor Nominal 100.0-9999.0 RPM Size related Enter motor nominal speed from nameplate data Speed 1-26 Motor Cont.
  • Page 15 How to Programme ® HVAC Basic Drive FC 101 Programming Guide Parameter Range Default Function 6-11 Terminal 53 High 0-10 V 10 V Enter the voltage that corresponds to the high Voltage reference value 6-12 Terminal 53 Low 0-20 mA Enter the current that corresponds to the low Current reference value...
  • Page 16 How to Programme ® HVAC Basic Drive FC 101 Programming Guide 0-03 Regional Settings Power kW/50 Hz 0-06 Grid Type 200-240V/50Hz/Delta 1-00 Con guration Mode Closed Loop 1-10 Motor Type Asynchronous PM motor Asynchronous Motor 1-20 Motor Power 1-24 Motor Current 1.10 1-25 Motor nominal speed 1-22 Motor Voltage...
  • Page 17 How to Programme ® HVAC Basic Drive FC 101 Programming Guide Closed Loop Set-up Wizard Parameter Range Default Function 0-03 Regional Settings [0] International [1] US 0-06 GridType [0] -[[132] see start -up wizard Size selected Select operating mode for restart upon for open loop application reconnection of the frequency converter to mains voltage after power down...
  • Page 18 How to Programme ® HVAC Basic Drive FC 101 Programming Guide Parameter Range Default Function 1-73 Flying Start [0] Disabled Select [1] Enable to enable the frequency [1] Enabled converter to catch a spinning motor. I.e. fan applications. When PM is selected, Flying Start is enabled.
  • Page 19 How to Programme ® HVAC Basic Drive FC 101 Programming Guide Motor Set-up The Quick Menu Motor Set-up guides through the needed motor parameters. Parameter Range Default Function 0-03 Regional Settings [0] International [1] US 0-06 GridType [0] -[132] see start -up wizard for Size selected Select operating mode for restart open loop application...
  • Page 20: Main Menu

    Once the set-up of a frequency converter is complete, setting's value from another different value, the parameter Danfoss recommends to store the data in the LCP or on a will NOT be listed in Changes Made. PC via MCT 10 Setup Software tool.
  • Page 21 How to Programme ® HVAC Basic Drive FC 101 Programming Guide Reconnect the mains supply - the frequency converter is now reset. Except the following parameters: 8-30 Protocol 8-31 Address 8-32 Baud Rate 8-33 Parity / Stop Bits 8-35 Minimum Response Delay 8-36 Maximum Response Delay 8-37 Maximum Inter-char delay 8-70 BACnet Device Instance...
  • Page 22: Parameters

    Parameters ® HVAC Basic Drive FC 101 Programming Guide 3 Parameters 0-04 Operating State at Power-up 3.1 Main Menu - Operation and Display - Option: Function: Group 0 as before the frequency converter was powered down. Parameters related to the fundamental functions of the Forced Uses saved reference [1] to stop the frequency frequency converter, function of the LCP keys and configu-...
  • Page 23 Parameters ® HVAC Basic Drive FC 101 Programming Guide 0-06 GridType 0-10 Active Set-up Option: Function: Option: Function: [131] 525-600V/60Hz/Delta Select the set-up in which the frequency converter is to operate. [132] 525-600V/60Hz Set-up 1 Set-up 1 is active. 0-07 Auto DC Braking Set-up 2 Set-up 2 is active.
  • Page 24 Parameters ® HVAC Basic Drive FC 101 Programming Guide Custom Readout (Value) 0-30 Custom Readout Unit P 16-09 Custom Readout Option: Function: Unit P 0-30 [31] kg/min Max value P 0-32 [32] kg/h [33] t/min [34] [40] [41] m/min [45] Min value [60] Degree Celsius...
  • Page 25 Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.1.5 0-5* Copy/Save 0-37 Display Text 1 Range: Function: Copy parameter settings between set-ups and to/from the [0 - 0 ] In this parameter it is possible to write an individual LCP.
  • Page 26: Main Menu - Load And Motor - Group

    Parameters ® HVAC Basic Drive FC 101 Programming Guide 1-03 Torque Characteristics 3.2 Main Menu - Load and Motor - Group 1 Option: Function: Variable For speed control of centrifugal pumps and fans. Parameters related to the motor nameplate load compen- Torque Also to be used when controlling more than sations and application load type.
  • Page 27 Parameters ® HVAC Basic Drive FC 101 Programming Guide 1-17 Voltage filter time const. 1-10 Motor Construction 1-20 Motor Power [kW] Select the motor construction type. Other parameters will be 1-22 Motor Voltage changed when changing motor type selection 1-23 Motor Frequency Option: Function: 1-24 Motor Current...
  • Page 28 Parameters ® HVAC Basic Drive FC 101 Programming Guide 1-16 High Speed Filter Time Const 1-20 Motor Power Range: Function: Range: Function: Size related [ 0.01 - High pass-filter damping time constant [23] 55 kW - 75 hp 20 s] determines the response time to load [24] 75 kW - 100 hp...
  • Page 29 Parameters ® HVAC Basic Drive FC 101 Programming Guide NOTICE 1-29 Automatic Motor Adaption (AMA) Option: Function: If one of the settings in parameter group 1-2* Motor NOTICE Data is changed, the advanced motor parameters, 1-30 Stator Resistance (Rs) to 1-39 Motor Poles, will return This parameter cannot be adjusted to default setting.
  • Page 30 Parameters ® HVAC Basic Drive FC 101 Programming Guide 1-39 Motor Poles 1-55 U/f Characteristic - U Range: Function: Range: Function: NOTICE [2 - Size related [0 - Enter voltage at each frequency point to 100 ] 999 V] manually form a U/f characteristic This parameter cannot be adjusted matching motor.
  • Page 31 Parameters ® HVAC Basic Drive FC 101 Programming Guide 1-63 Slip Compensation Time Constant 1-73 Flying Start Range: Function: Option: Function: 0.1 s [ 0.05 - Enter the slip compensation reaction speed. A below 2.5%-5%, in the time set in 2-07 Parking Time.
  • Page 32 Option: Function: Using ETR (Electronic Thermal Relay), the motor temperature is calculated based on frequency, speed and time. Danfoss recommends using the ETR function, if a thermistor is not present. The functionality is the same for asynchronous motors and PM motors.
  • Page 33: Main Menu - Brakes - Group

    Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.3 Main Menu - Brakes - Group 2 2-06 Parking Current Range: Function: 2-00 DC Hold/Motor Preheat Current 100 % [0 - Set current as percentage of rated motor Range: Function: 150 %] current, 1-24 Motor Current.
  • Page 34: Main Menu - Reference/Ramps - Group

    Parameters ® HVAC Basic Drive FC 101 Programming Guide 3-10 Preset Reference 3.4 Main Menu - Reference/Ramps - Group Range: Function: [-100 - Enter up to 8 different preset references (0-7) in 100 %] this parameter, using array programming. Select 3.4.1 3-0* Reference Limits Preset Reference bit 0/1/2 [16] , [17] or [18] for the corresponding digital inputs in parameter...
  • Page 35 Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.4.3 3-4* Ramp 1 3-16 Reference 2 Source Option: Function: Configure the ramp parameter, ramping times, for each of Select the input to be used for the the 2 ramps (parameter group 3-4* Ramp 1 and parameter second reference signal.
  • Page 36 Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.4.4 3-5* Ramp 2 Selecting ramp parameters, see parameter group 3-4* Ramp 1. 3-51 Ramp 2 Ramp Up Time Range: Function: Size [0.05 Enter acceleration time from 0 Hz to related - 3600 1-23 Motor Frequency if Asynchronous motor is selected.
  • Page 37: Main Menu - Limits/Warnings - Group

    Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.5 Main Menu - Limits/Warnings - Group 4 4-18 Current Limit Range: Function: 3.5.1 4-1* Motor Limits 4-18 Current Limit is not automatically reset to the default setting. Define current and speed limits for the motor, and the reaction of the frequency converter when the limits are 4-19 Max Output Frequency exceeded.
  • Page 38 Parameters ® HVAC Basic Drive FC 101 Programming Guide 4-51 Warning Current High 4-58 Missing Motor Phase Function Range: Function: Option: Function: NOTICE Size [ 0.0 - Enter the I value. When the motor HIGH related 194.0 A] current exceeds this limit, a bit in the This parameter cannot be adjusted while the statusword is set.
  • Page 39 Parameters ® HVAC Basic Drive FC 101 Programming Guide NOTICE Smaller frequency converters have a ramp time of 3 seconds which can make it difficult to set the bypass speeds. Adjust the ramp times in 3-41 Ramp 1 Ramp Up Time and 3-42 Ramp 1 Ramp Down Time.
  • Page 40: Main Menu - Digital In/Out - Group

    Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.6 Main Menu - Digital In/Out - Group 5 Digital input Description function 3.6.1 5-0* Digital I/O Mode [5] DC-brake inverse Inverted input for DC braking (NC). Stops motor by energising it with DC current for Parameters for configuring the input and output using a certain time period, see 2-01 DC Brake NPN and PNP.
  • Page 41 Parameters ® HVAC Basic Drive FC 101 Programming Guide Digital input Description Digital input Description function function [19] Freeze reference Freeze actual reference. The frozen [52] Run permissive The input terminal, for which the Run reference is now the point of enable/ permissive has been programmed must condition for Speed up and Speed down be logic “1”...
  • Page 42 Parameters ® HVAC Basic Drive FC 101 Programming Guide Digital input Description 5-10 Terminal 18 Digital Input function Parameter for configuring the input function on input terminal 18. Refer to Table 3.3 for setting options. [63] Counter B (up) Input for increment counting in the SLC Option: Function: counter.
  • Page 43 Parameters ® HVAC Basic Drive FC 101 Programming Guide 5-12 Terminal 27 Digital Input 5-13 Terminal 29 Digital Input Parameter for configuring the input function on input terminal Parameter for configuring the input function on input terminal Option: Function: Option: Function: No operation [16]...
  • Page 44 Parameters ® HVAC Basic Drive FC 101 Programming Guide Running / no The output speed is higher than the [35] External External Interlock function has been warning speed set in 1-81 Min Speed for Function Interlock activated via one of the digital inputs. at Stop [RPM].
  • Page 45 Parameters ® HVAC Basic Drive FC 101 Programming Guide [80] SL Digital See 13-52 SL Controller Action. The input indicated by the LED light above [Hand Output A will go high whenever the Smart Logic on]. Action [38] Set dig. out. A high is [169] Drive in auto The output is high when the frequency executed.
  • Page 46 Parameters ® HVAC Basic Drive FC 101 Programming Guide 5-40 Function Relay 5-40 Function Relay Array (Relay 1 [0], Relay 2 [1]) Array (Relay 1 [0], Relay 2 [1]) Select options to define the function of the relays. Select options to define the function of the relays. The selection of each mechanical relay is realised in an array The selection of each mechanical relay is realised in an array parameter.
  • Page 47 Parameters ® HVAC Basic Drive FC 101 Programming Guide 5-40 Function Relay 5-40 Function Relay Array (Relay 1 [0], Relay 2 [1]) Array (Relay 1 [0], Relay 2 [1]) Select options to define the function of the relays. Select options to define the function of the relays. The selection of each mechanical relay is realised in an array The selection of each mechanical relay is realised in an array parameter.
  • Page 48 Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.6.5 5-5* Pulse Input Selected Event The pulse input parameters are used to define an appropriate window for the impulse reference area by Relay configuring the scaling and filter settings for the pulse output inputs.
  • Page 49 Parameters ® HVAC Basic Drive FC 101 Programming Guide 5-53 Term. 29 High Ref./Feedb. Value Range: Function: [-4999 - 4999 ] Enter the high reference value Size [-999999.999 - [RPM] for the motor shaft related 999999.999 speed and the high feedback ReferenceFeed- value, see also 5-58 Term.
  • Page 50: Main Menu - Analog In/Out - Group

    Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.7.2 6-1* Analog Input 53 3.7 Main Menu - Analog In/Out - Group 6 Parameter group for setting up the analog I/O configu- Parameters for configuring the scaling and limits for ration and the digital output.
  • Page 51 Parameters ® HVAC Basic Drive FC 101 Programming Guide 6-16 Terminal 53 Filter Time Constant 6-25 Terminal 54 High Ref./Feedb. Value Range: Function: Range: Function: but also increases the time delay through the Size related [-4999 - Enter the reference or feedback value filter.
  • Page 52 Parameters ® HVAC Basic Drive FC 101 Programming Guide 6-72 Terminal 45 Digital Output 6-72 Terminal 45 Digital Output Option: Function: Option: Function: Select the function of [82] SL digital output C Terminal 45 as a [83] SL digital output D digital current output.
  • Page 53 Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.7.5 6-9* Analog/Digital Output 42 6-92 Terminal 42 Digital Output Option: Function: Parameters for configuring the limits for analog/digital [17] Above speed, high output Terminal 42. Analog outputs are current outputs: [19] Below feedback, low 0/4-20 mA.
  • Page 54 Parameters ® HVAC Basic Drive FC 101 Programming Guide 6-94 Terminal 42 Output Max Scale Range: Function: [0 - Scale for the maximum output (20 mA) of the scaling at Terminal 42. Set the value to be the percentage of the full range of the variable selected in 6-91 Terminal 42 Analog Output.
  • Page 55: Main Menu - Communications And Options - Group

    Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.8.2 8-3* FC Port Settings 3.8 Main Menu - Communications and Options - Group 8 3.8.1 8-0* General Settings 8-30 Protocol Option: Function: 8-01 Control Site Select the protocol for the integrated RS-485 Option: Function: port.
  • Page 56 Parameters ® HVAC Basic Drive FC 101 Programming Guide 8-33 Parity / Stop Bits 8-51 Quick Stop Select Option: Function: Option: Function: [1] Odd Parity, 1 Stop Select control of the Quick Stop function via the terminals (digital input) and/or via the bus. NOTICE [2] No Parity, 1 Stop Bit [3] No Parity, 2 Stop...
  • Page 57 Parameters ® HVAC Basic Drive FC 101 Programming Guide 8-53 Start Select 8-56 Preset Reference Select Option: Function: Option: Function: Logic Activates Start command via the serial Select control of the frequency converter Preset communication port, AND additionally via one of Reference selection via the terminals (digital the digital inputs.
  • Page 58 Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.8.5 8-8* FC Port Diagnostics These parameters are used for monitoring the Bus communication via the FC Port. 8-80 Bus Message Count Range: Function: [0 - 65536 ] This parameter shows the number of valid telegrams detected on the bus.
  • Page 59: Main Menu - Smart Logic - Group

    Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.9 Main Menu - Smart Logic - Group 13 13-00 SL Controller Mode Option: Function: 3.9.1 13-** Prog. Features Select [1] On to enable the Smart Logic Control to start when a start command is present, e.g. via a Smart Logic Control (SLC) is a sequence of user defined digital input.
  • Page 60 Parameters ® HVAC Basic Drive FC 101 Programming Guide 13-01 Start Event 13-02 Stop Event Option: Function: Option: Function: [27] Logic rule 1 Use the result of logic rule 1 in the In range See 13-01 Start Event for further logic rule.
  • Page 61 Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.9.3 13-1* Comparators 13-02 Stop Event Option: Function: Comparators are used for comparing continuous variables [34] Digital input DI19 (i.e. output frequency, output current, analog input etc.) to [35] Digital input DI27 Use the value of DI27 in the logic rule fixed preset values.
  • Page 62 Parameters ® HVAC Basic Drive FC 101 Programming Guide 13-11 Comparator Operator Par. 13-41 Par. 13-43 Logic Rule Operator 1 Logic Rule Operator 2 Par. 13-40 Array [6] Logic Rule Boolean 1 Option: Function: Par. 13-42 Logic Rule Boolean 2 .
  • Page 63 Parameters ® HVAC Basic Drive FC 101 Programming Guide 13-40 Logic Rule Boolean 1 13-40 Logic Rule Boolean 1 Array [6] Array [6] Option: Function: Option: Function: [23] Comparator 1 Use the result of comparator 1 in the [61] Logic rule 5 Use the result of logic rule 5 in the logic rule.
  • Page 64 Parameters ® HVAC Basic Drive FC 101 Programming Guide 13-42 Logic Rule Boolean 2 13-43 Logic Rule Operator 2 Array [6] Array [6] Option: Function: Option: Function: [19] Warning Disabled [20] Alarm (trip) [21] Alarm (trip lock) [22] Comparator 0 AND NOT [23] Comparator 1 OR NOT...
  • Page 65 Parameters ® HVAC Basic Drive FC 101 Programming Guide 13-44 Logic Rule Boolean 3 13-51 SL Controller Event Array [6] Array [20] Option: Function: Option: Function: [42] Auto Reset Trip [35] Digital input DI27 [50] Comparator 4 [36] Digital input DI29 [51] Comparator 5 [39] Start command [60] Logic rule 4...
  • Page 66 Parameters ® HVAC Basic Drive FC 101 Programming Guide 13-52 SL Controller Action 13-52 SL Controller Action Array [20] Array [20] Option: Function: Option: Function: [18] Select ramp 1 Selects ramp 1 [71] Start Timer 4 Starts timer 4, see 13-20 SL Controller Timer for further description.
  • Page 67: Main Menu - Special Functions - Group

    Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.10 Main Menu - Special Functions - Group 14-08 Damping Gain Factor Range: Function: 96 % [0 - 100 %] Damping factor for DC-Link Voltage 3.10.1 14-0* Inverter Switching Compensation. 14-01 Switching Frequency 3.10.2 14-1* Mains On/Off Option: Function:...
  • Page 68 Parameters ® HVAC Basic Drive FC 101 Programming Guide 14-20 Reset Mode 14-28 Production Settings Option: Function: Option: Function: Automatic reset x 3 Service reset Automatic reset x 4 Software Reset Automatic reset x 5 14-29 Service Code Automatic reset x 6 Range: Function: Automatic reset x 7...
  • Page 69 Parameters ® HVAC Basic Drive FC 101 Programming Guide 14-51 DC-Link Voltage Compensation Option: Function: Disables DC Link Compensation. Enables DC Link Compensation. 14-52 Fan Control Option: Function: Only valid for the following frequency converters: 380-480 V, 30-90 kW. Auto Auto Low Temp Env.
  • Page 70: Main Menu - Drive Information - Group

    Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.11 Main Menu - Drive Information - Group 15-06 Reset kWh Counter Option: Function: Reset counter Select [1] Reset and press [OK] to reset the Parameter group containing frequency converter kWh counter to zero (see 15-02 kWh information such as operating data, hardware configu- Counter).
  • Page 71 Parameters ® HVAC Basic Drive FC 101 Programming Guide 15-42 Voltage 15-98 Drive Identification Range: Function: Range: Function: [0 - 0 ] View the FC type code. The read-out is identical to [0 - 0 ] the frequency converter series power field of the type code definition, characters 11-12.
  • Page 72: Main Menu - Data Readouts - Group

    Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.12 Main Menu - Data Readouts - Group 16 16-03 Status Word Range: Function: [0 - 65535 ] View the Status word sent from the frequency 3.12.1 16-0* General Status converter via the serial communication port in hex code.
  • Page 73 Parameters ® HVAC Basic Drive FC 101 Programming Guide 16-11 Power [hp] 16-36 Inv. Nom. Current Range: Function: Range: Function: 0 hp [0 - 1000 View the DC link power in hp. The value [0 - 655.35 View the inverter nominal current, which shown is calculated on the basis of the should match the nameplate data on the actual motor voltage and motor current.
  • Page 74 Parameters ® HVAC Basic Drive FC 101 Programming Guide 16-61 Terminal 53 Setting 16-67 Pulse Input #29 [Hz] Option: Function: Range: Function: View the setting of input terminal 53. [0 - 130000 ] View the actual frequency rate on terminal Current = 0;...
  • Page 75 Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.12.7 16-9* Diagnosis Read-Outs 16-90 Alarm Word Range: Function: [0 - 0xFFFFFFFFUL ] View the alarm word sent via the serial communication port in hex code. 16-91 Alarm Word 2 Range: Function: [0 - 0xFFFFFFFFUL ] View the alarm word 2 sent via the serial communication port in hex code.
  • Page 76: Main Menu - Data Readouts 2 - Group

    Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.13 Main Menu - Data Readouts 2 - Group 20-81 PI Normal/ Inverse Control Option: Function: Normal Causes the frequency converter’s output frequency Parameters in this group are array parameters, where up to to decrease when the feedback is greater than the 10 fault logs can be viewed.
  • Page 77 Parameters ® HVAC Basic Drive FC 101 Programming Guide 20-94 PI Integral Time Range: Function: 20 s [0.10 - Enter the process controller integral time. 9999 s] Obtain quick control through a short integral time, though if the integral time is too short, the process becomes unstable.
  • Page 78: Main Menu - Application Functions - Group

    Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.15 Main Menu - Application Functions - The frequency converter activates 1-80 Function at Stop. The frequency converter is now in Sleep Group 22 mode. 3.15.1 22-4* Sleep Mode When error between Reference and Feedback is greater than 22-44 Wake-Up Ref./FB Diff, and the The purpose of sleep mode is to allow the frequency condition last more than 22-41 Minimum Sleep...
  • Page 79 Parameters ® HVAC Basic Drive FC 101 Programming Guide NOTICE 22-45 Setpoint Boost Range: Function: Do not set 14-20 Reset Mode, to [13] Infinite auto reset, when 22-60 Broken Belt Function is set to [2] Trip. Doing control, it is advantageous to increase so causes the frequency converter to continuously cycle the system pressure before the motor is between running and stopping when a broken belt...
  • Page 80: Main Menu - Application Functions 2 - Group

    Fire Mode. In no event shall Danfoss be liable to the end user NOTICE or any other party for any direct or indirect, special or...
  • Page 81 Parameters ® HVAC Basic Drive FC 101 Programming Guide 3.16.2 24-1* Drive Bypass 24-05 FM Preset Reference Range: Function: The frequency converter includes a feature, which can be [-100 - 100 Enter the required preset reference/set point used to automatically activate an external electro- as a percentage of the Fire Mode Max mechanical bypass in case of the event of a Fire Mode Reference set in Hz.
  • Page 82 Parameters ® HVAC Basic Drive FC 101 Programming Guide 24-10 Drive Bypass Function Option: Function: if the timer expires before reset attempts have completed. 24-11 Drive Bypass Delay Time Range: Function: [0 - Programmable in 1 s increments. Once the Bypass Function is activated in accordance with the setting in 24-10 Drive Bypass Function, the Bypass Delay Timer begins to operate.
  • Page 83: Alarms And Warnings

    Troubleshooting ® HVAC Basic Drive FC 101 Programming Guide 4 Troubleshooting If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked, 4.1 Alarms and Warnings see Table 4.1. A warning or an alarm is signalled by the relevant LED on CAUTION the front of the frequency converter and indicated by a...
  • Page 84 Troubleshooting ® HVAC Basic Drive FC 101 Programming Guide No. Description Warning Alarm Trip Lock Parameter Reference AMA check U and I AMA low I AMA motor too big AMA motor too small AMA Parameter out of range AMA interrupted by user AMA timeout AMA internal fault Current limit...
  • Page 85: Alarm Words

    Troubleshooting ® HVAC Basic Drive FC 101 Programming Guide 4.2 Alarm Words 4.3 Warning Words 16-90 Alarm 16-91 Alarm Word Word 2 16-92 Warning 16-93 Warning Word Word 2 Pwr.Card Temp ServiceTrip, Pwr.Card Temp Earth Fault Typecode Earth Fault Sparepart Ctrl.
  • Page 86: Extended Status Words

    Troubleshooting ® HVAC Basic Drive FC 101 Programming Guide 4.4 Extended Status Words 4.5 List of Warnings and Alarms WARNING/ALARM 2, Live zero error 16-94 Ext. 16-95 Ext. Status This warning or alarm will only appear if programmed by Status Word Word 2 the user in 6-01 Live Zero Timeout Function.
  • Page 87 Troubleshooting ® HVAC Basic Drive FC 101 Programming Guide Troubleshooting: Check that the motor size matches the frequency Compare the output current shown on the LCP converter. with the frequency converter rated current. Incorrect motor data in parameters 1-20 through Compare the output current shown on the LCP 1-25.
  • Page 88 This warning is based on the temperature sensor in the ALARM 38, Internal fault IGBT module. It may be necessary to contact your Danfoss supplier. ALARM 70, Illegal power section configuration ALARM 44, Earth fault II The control card and power card are incompatible. Contact...
  • Page 89: Parameter Lists

    Parameter Lists ® HVAC Basic Drive FC 101 Programming Guide 5 Parameter Lists 5.1 Parameter Options 5.1.1 Default Settings Changes during operation ”TRUE” means that the parameter can be changed while the frequency converter is in operation and “FALSE” means that the frequency converter must be stopped before a change can be made.
  • Page 90: Operation/Display

    Parameter Lists ® HVAC Basic Drive FC 101 Programming Guide 5.1.2 0-** Operation/Display Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion index operation 0-0* Basic Settings 0-01 Language [0] English 1 set-up TRUE Uint8 0-03 Regional Settings ExpressionLimit 1 set-up...
  • Page 91 Parameter Lists ® HVAC Basic Drive FC 101 Programming Guide Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion index operation 1-26 Motor Cont. Rated Torque ExpressionLimit All set-ups FALSE Uint32 1-29 Automatic Motor Adaption (AMA) [0] Off 1 set-up FALSE...
  • Page 92: Brakes

    Parameter Lists ® HVAC Basic Drive FC 101 Programming Guide 5.1.4 2-** Brakes Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion index operation 2-0* DC-Brake 2-00 DC Hold/Motor Preheat Current 50 % All set-ups TRUE Uint16 2-01 DC Brake Current...
  • Page 93: Digital In/Out

    Parameter Lists ® HVAC Basic Drive FC 101 Programming Guide Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion operation index 4-40 Warning Freq. Low ExpressionLimit All set-ups TRUE uint16 4-41 Warning Freq. High ExpressionLimit All set-ups TRUE uint16 4-5* Adj.
  • Page 94: Analog In/Out

    Parameter Lists ® HVAC Basic Drive FC 101 Programming Guide 5.1.8 6-** Analog In/Out Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion index operation 6-0* Analog I/O Mode 6-00 Live Zero Timeout Time 10 s All set-ups TRUE Uint8...
  • Page 95: Comm. And Options

    Parameter Lists ® HVAC Basic Drive FC 101 Programming Guide 5.1.9 8-** Comm. and Options Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion operation index 8-0* General Settings 8-01 Control Site [0] Digital and ctrl.word All set-ups TRUE Uint8...
  • Page 96: Special Functions

    Parameter Lists ® HVAC Basic Drive FC 101 Programming Guide Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion operation index 13-03 Reset SLC [0] Do not reset SLC 1 set-up TRUE Uint8 13-1* Comparators 13-10 Comparator Operand [0] Disabled 1 set-up...
  • Page 97: Drive Information

    Parameter Lists ® HVAC Basic Drive FC 101 Programming Guide 5.1.12 15-** Drive Information Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion index operation 15-0* Operating Data 15-00 Operating Hours All set-ups TRUE Uint32 15-01 Running Hours All set-ups TRUE...
  • Page 98: Info & Readouts

    Parameter Lists ® HVAC Basic Drive FC 101 Programming Guide 16-36 Inv. Nom. Current 1 set-up TRUE Uint16 16-37 Inv. Max. Current 1 set-up TRUE Uint16 16-38 SL Controller State 0 N/A 1 set-up TRUE Uint8 16-5* Ref. & Feedb. 16-50 External Reference 1 set-up...
  • Page 99: Drive Closed Loop

    Parameter Lists ® HVAC Basic Drive FC 101 Programming Guide 5.1.15 20-** Drive Closed Loop Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion index operation 20-0* Feedback 20-00 Feedback 1 Source [0] No function All set-ups TRUE Uint8 20-01...
  • Page 100 ® Index HVAC Basic Drive FC 101 Programming Guide Index Comparator Operand....................59 Operator....................59 Value..................... 60 Action At Inverter Fault..............66 Comparators..................59 Active Set-up..................21 Control Site......................53 Address....................53 Timeout Time..................53 Advanced Vector Control..............4 Word..................... 70 AEO......................
  • Page 101 ® Index HVAC Basic Drive FC 101 Programming Guide Control....................67 Jog..................... 4, 38 Monitor....................67 Ramp Time..................34 Speed [Hz]................... 32 Fault Messages..................84 Closed Loop..................74 Port Diagnostics................56 KWh Counter..................68 Port Settings..................53 Feedback Feedback..................... 74 Language....................
  • Page 102 ® Index HVAC Basic Drive FC 101 Programming Guide Motor Preset Control Principle................24 Ref Bit 0....................38 Current..................26, 71 Ref Bit 1....................38 Frequency................... 26 Ref Bit 2....................38 Magnetisation At Zero Speed............28 Reference.................... 32 Poles...................... 28 Relative Reference................
  • Page 103 ® Index HVAC Basic Drive FC 101 Programming Guide Semi-Auto Bypass Set-up..............37 Serial Communication................44 Terminal Communication Port................. 4 18 Digital Input................. 40 19 Digital Input................. 40 Setpoint Boost..................77 27 Digital Input................. 41 Set-up Copy................... 23 29 Digital Input................. 41 42 Analog Output................
  • Page 104 130R0221 MG18B302 Rev. 2013-09-02 *MG18B302*...