WAGO-I/O-SYSTEM 750
750-494 3-Phase Power Measurement Module
A. User Scaling OFF, Measurement without Current Transformer
Current
Register 32,
bits 12 ... 14
Register 39 ... 41
(D-CTR)
Process value
Scaling factor PI
Equation
Measured value
Active Power
Register 32,
bits 12 ... 14
Register 39 ... 41
(D-CTR)
Process value
Scaling factor PI
Equation
Measured value
Active Energy
Register 32,
bits 12 ... 14
Register 39 ... 41
(D-CTR)
Register 35*
Process value
Scaling factor PI
Equation
Measured value
* Register 35: The set value defines the scaling factor PI for energy values.
B. User Scaling ON, Measurement with Current Transformer
Current
Register 32,
bits 12 ... 14
Register 39 ... 41
(D-CTR)
Process value
Scaling factor PI
Equation
Measured value
Manual
Version 1.2.0
1A-varints
0
0x0001 (1)
0x000010A9 (4250)
0.0001A
Measured value = Process value x Scaling factor PI
0.425 A
1A-varints
0
0x0001 (1)
0x00002639 (9785)
0.01W
Measured value = Process value x Scaling factor PI
97.85 W
1A-varints
0
0x0001 (1)
1
0x000022ED (8941)
0.01Wh
Measured value = Process value x Scaling factor PI
89.41 Wh
1A-varints
1
0x002D (45)
0x0005E250 (385616)
0.0001A
Measured value = Process value x Scaling factor PI
38.562 A
Process Image
5A-variants
0
0x0001 (1)
0x00002062 (8290)
0.0005A
4.145 A
5A-variants
0
0x0001 (1)
0xFFFFC618 (-14824)
0.05W
-741.20 W
5A-variants
0
0x0001 (1)
3
0x00001126 (4390)
5Wh
21950 Wh
5A-variants
1
0x0028 (40)
0x0003C9D1 (248273)
0.0005A
124.137 A
65