WAGO-I/O-SYSTEM 750
750-451 8 AI RTD
Register
35
Bit 11: Diagnosis, user limiting value overrange
0
1*
Bit 12: Diagnosis, short circuit
0
1*
Bit 13: Diagnosis, wire break
0
1*
Bit 14: Group error
0
1*
Bit 15: Global enable and disable diagnostic functions
0
1*
*)
Default setting
Table 49: Register 36
Register
36
Bit 0 ... 15: Line resistance
0 ... 65535
0 ... FFFF
0 ... 65.535
Table 50: Register 37
Register
37
Bit 0 ... 15: User scaling Offset
–32768 ... 32767
8000 ... 7FFF
–262144 ... 262136
FFFC0000 ... 03FFF8 Value range (scaled), hexadecimal, 16-bit integer
The user calibration is enabled if bit 6 in register 35 is not set.
Manual
Version 1.1.0
Function
Channel configuration
Diagnostics disabled
Diagnostics enabled
Diagnostics disabled
Diagnostics enabled
Diagnostics disabled
Diagnostics enabled
Diagnostics disabled
Diagnostics enabled
Diagnostics disabled
Diagnostics enabled
Function
Line resistance
Value range (raw), decimal, 16-bit unsigned integer
Value range (raw), hexadecimal, 16-bit unsigned integer
Value range (scaled), decimal, 16-bit unsigned integer
Resolution:
Unit
Equation:
Function
User calibration
Offset
Value range (raw), decimal, 16-bit integer
Value range (raw), hexadecimal, 16-bit integer
Value range (scaled), decimal, 16-bit integer
Resolution:
Unit
Equation:
Memory
Access
EEPROM
Memory
Access
EEPROM
1/1000
Ohm
R = R(raw) – Reg37
Memory
Access
EEPROM
8
–
Raw value(corr) =
((raw value(ADC) × Reg38) / 32768) × (Reg37 × 8)
Commissioning
Default setting
R/W
0xFF10
Default setting
R/W
0x0000
Default setting
R/W
0x0000
65