132 Appendix
11.4.2.7
Tables 60, 61 (Valve Adjustment, Valve 1, Valve 2)
Tables 60 and 61 are identically structured. As an example, Table 60 will be
explained for Valve 1 here.
Table 90: Parameters, Table 60 (Valve Adjustment, Valve 1)
Register
0
1
2
3
4
5
Manual
Version 1.3.1, valid from FW/HW-Version 01/01
Name,
Bits
Type
Explanation
VA_TRIG,
0 ... 15
UINT16
VA_MIN_A,
0 ... 15
UINT16
VA_MAX_A,
0 ... 15
UINT16
VA_MIN_B,
0 ... 15
UINT16
VA_MAX_B,
0 ... 15
UINT16
WAGO I/O System 750/753
750-632 Proportional Valve Module
Value/Range
Description
(Default)
(Default: 1)
(reserved)
0 ... 9000
n * 0.01%
(Default: 0)
Response threshold,
Valve 1
Quadrant I and III
0 ... 9000
n * 0.01%
(Default: 0)
Compensation for the
dead zone, Valve 1,
Quadrant I
1000 ... 10000
n * 0.01%
(Default:
Maximum output signal,
10000)
Valve 1, Quadrant I
0 ... 9000
n * 0.01%
(Default: 0)
Compensation for the
dead zone, Valve 1,
Quadrant III
1000 ... 10000
n * 0.01%
(Default:
Maximum output signal,
10000)
Valve 1, Quadrant III