Set the assertion timeout for an environmental sensor:
sensor externalsensor <n> <sensor type> assertionTimeout <as_value>
Variables:
<n> is the ID number of the environmental sensor that you want to configure. The ID number is available in the PRO3X web
interface or using the command "show externalsensors <n>" in the CLI. It is an integer starting at 1.
<sensor type> is one of the following numeric sensor types:
Sensor types
absoluteHumidity
relativeHumidity
temperature
airPressure
airFlow
vibration
Note: If the specified sensor type does not match the type of the specified environmental sensor, this error message
appears: "Specified sensor type 'XXX' does not match the sensor's type (<sensortype>)," where XXX is the specified sensor
type, and <sensortype> is the correct sensor type.
<option> is one of the options: enable, disable or a numeric value.
Option
enable
disable
A numeric value
<hy_value> is a numeric value that is assigned to the hysteresis for the specified environmental sensor.
<as_value> is a number in samples that is assigned to the assertion timeout for the specified environmental sensor. It ranges
between 1 and 100.
Description
Absolute humidity sensors
Relative humidity sensors
Temperature sensors
Air pressure sensors
Air flow sensors
Vibration sensors
Description
Enables the specified threshold for a specific
environmental sensor.
Disables the specified threshold for a specific
environmental sensor.
Sets a value for the specified threshold of a specific
environmental sensor and enables this threshold at
the same time.
PRO3X User Guide – Command Line Interface (CLI)
Using the PRO3X Command Line Interface (CLI)
147 of 182
Need help?
Do you have a question about the Server Technology PRO3X and is the answer not in the manual?