Example - Default Upper Thresholds for Temperature
It is assumed that your preferred measurement unit for temperature is set to degrees Celsius. Then the following command
sets the default Upper Warning threshold to 20 Celsius and Upper Critical threshold to 24 Celsius for all temperature sensors.
defaultThresholds temperature upperWarning 20 upperCritical 24
Sensor Threshold Configuration Commands
A sensor configuration command begins with sensor. You can use the commands to configure the threshold, hysteresis and
assertion timeout values for any sensor associated with the following items:
▪
Inlets
▪
Inlet poles (for three-phase PDUs only)
▪
Overcurrent protectors
▪
Environmental sensors
It is permitted to assign a new value to the threshold at any time regardless of whether the threshold has been enabled.
Commands for Inlet Sensors
A sensor configuration command for inlets begins with sensor inlet.
You can configure various inlet sensor threshold settings at a time by combining multiple commands. Set the Upper Critical
threshold for an inlet sensor:
sensor inlet <n> <sensor type> upperCritical <option>
Set the Upper Warning threshold for an inlet sensor:
sensor inlet <n> <sensor type> upperWarning <option>
Set the Lower Critical threshold for an inlet sensor:
sensor inlet <n> <sensor type> lowerCritical <option>