Set the Lower Warning threshold for an inlet sensor:
sensor inlet <n> <sensor type> lowerWarning <option>
Set the deassertion hysteresis for an inlet sensor:
sensor inlet <n> <sensor type> hysteresis <hy_value>
Set the assertion timeout for an inlet sensor:
sensor inlet <n> <sensor type> assertionTimeout <as_value>
Variables:
<n> is the number of the inlet that you want to configure. For a single-inlet PDU, <n> is always 1.
<sensor type> is one of the following sensor types:
Sensor type
current
voltage
activePower
apparentPower
powerFactor
activeEnergy
unbalancedCurrent
lineFrequency
phaseAngle
Note: If the requested sensor type is not supported, the "Sensor is not available" message is displayed.
Description
Current sensor
Voltage sensor
Active power sensor
Apparent power sensor
Power factor sensor
Active energy sensor
Unbalanced load sensor
Line frequency sensor
Inlet phase angle sensor
PRO3X User Guide – Command Line Interface (CLI)