Commands for Inlet Pole Sensors
A sensor configuration command for inlet poles begins with sensor inletpole. This type of command is available on a three-
phase PDU only. You can configure various inlet pole sensor threshold settings at a time by combining multiple commands.
Set the Upper Critical Threshold for an Inlet Pole:
sensor inletpole <n> <p> <sensor type> upperCritical <option>
Set the Upper Warning Threshold for an Inlet Pole:
sensor inletpole <n> <p> <sensor type> upperWarning <option>
Set the Lower Critical Threshold for an Inlet Pole:
sensor inletpole <n> <p> <sensor type> lowerCritical <option>
Set the Lower Warning Threshold for an Inlet Pole:
sensor inletpole <n> <p> <sensor type> lowerWarning <option>
Set the Inlet Pole's De-assertion Hysteresis:
sensor inletpole <n> <p> <sensor type> hysteresis <hy_value>
Set the Inlet Pole's Assertion Timeout:
sensor inletpole <n> <p> <sensor type> assertionTimeout <as_value>
PRO3X User Guide – Command Line Interface (CLI)
142 of 182