<option> is one of the options: enable, disable or a numeric value.
Option
Description
enable
Enables the specified threshold for a specific inlet
sensor.
disable
Disables the specified threshold for a specific inlet
sensor.
A numeric value
Sets a value for the specified threshold of a specific
inlet sensor and enables this threshold at the same
time.
<hy_value> is a numeric value that is assigned to the hysteresis for the specified inlet sensor.
<as_value> is a numeric value that is assigned to the assertion timeout for the specified inlet sensor.
Additional sensors supported by specific models:
Specific PRO3X models support some or all of the following sensors. The CLI command(s) listed above can be also applied to
the following sensors. Note that the measurement unit of current values in CLI is A, not mA.
Sensor type
peakCurrent
reactivePower
displacementPowerFact
or
residualCurrent
residualDCCurrent
Description
Peak current sensor
Reactive power sensor
Displacement power factor sensor
RCM current sensor
▪ For Type A, it is the sensor that detects
residual AC current.
▪ For Type B, it is the sensor that detects
both residual AC and DC current.
RCM DC current sensor - detects residual DC
current only.
Available only on PDUs with RCM Type B.
PRO3X User Guide – Command Line Interface (CLI)
Using the PRO3X Command Line Interface (CLI)
141 of 182