Securing A Cabinet; Securing A Pdu8000 - Huawei IDS2000 Installation Manual

Intelligent micro-modular data center 2000 mm high cabinet in dual-row aisle containment
Hide thumbs Also See for IDS2000:
Table of Contents

Advertisement

IDS2000 Intelligent Micro-Modular Data Center
Installation Guide (2000 mm High Cabinet in Dual-Row
Aisle Containment)
Figure 4-20 Checking aisle width (unit: mm)
----End

4.5.4 Securing a Cabinet

4.5.4.1 Securing a PDU8000

Procedure
Step 1 Place a PDU8000 onto a base and adjust its position. Adjust anchor bolts of the PDU8000
until the PDU8000 is 2000 mm high.
Step 2 Open the front and rear doors of the PDU8000.
Step 3 Secure the PDU8000 to the base using four M12 bolts, as shown in
Issue Draft A (2015-06-29)
Measure the aisle width between cabinet doors using a measuring tape.
If the aisle width is not 1200 mm, adjust the cabinet positions to ensure a 1200 mm wide aisle.
The length deviation between the two rows of cabinets must be within 1.5 mm, and the deviation
unevenness must be within 1 mm.
Exercise cautions when securing cabinets to prevent devices from tilting.
Before securing cabinets, move and place the cabinets onto bases with 3–4 persons for
safety purposes.
The front door surface of the PDU8000 should be aligned with that of the cabinet.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Hardware Installation
Figure
4-21.
36