Huawei IDS2000 Installation Manual page 41

Intelligent micro-modular data center 2000 mm high cabinet in dual-row aisle containment
Hide thumbs Also See for IDS2000:
Table of Contents

Advertisement

IDS2000 Intelligent Micro-Modular Data Center
Installation Guide (2000 mm High Cabinet in Dual-Row
Aisle Containment)
Figure 4-16 Pipe supports (unit: mm)
To damp noises generated by the equipment due to vibration, refrigerant pipe supports should
be installed as required by
Figure 4-17 Routing the refrigerant pipe (unit: mm)
Issue Draft A (2015-06-29)
The height of a U-shaped pipe clamp equals to the pipe diameter with thermal insulation foam minus
5 mm. The pipe supports are to be purchased by the customer.
The recommended material for pipe supports and clamps is 304 stainless steel.
Figure
When the direction of a refrigerant pipe changes, add a support at the position that is
1000 mm away from the changing point, as shown in
If the refrigerant pipe is straight, add a support every 2500 mm.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4-17.
4 Hardware Installation
Figure
4-16.