IDS2000 Intelligent Micro-Modular Data Center
Installation Guide (2000 mm High Cabinet in Dual-Row
Aisle Containment)
Figure 4-103 Connecting a 300 mm wide cable trough to a 600 mm wide cable trough
(1) Interconnecting wrench
----End
4.8.3 Installing an 800 mm Wide Cable Trough
An 800 mm wide cable trough is installed on the top of an 800 mm wide cabinet. The
installation method is similar to the method for installing a 600 mm wide cable trough. For
details, see
4.8.4 Installing End Panels for Cable Troughs
Context
Typically, end panels are installed only on cable troughs of cabinets on both ends of an aisle.
The BOM number is 21500561. The end panels are marked by different colors to facilitate the
recognition of power and signal cables. The red end panel should be installed on the trough
for power cables, and the blue end panel should be installed on the trough for signal cables.
Generally, a power cable trough is located close to the aisle containment, and the signal cable
trough is located far away from the aisle containment. This topic uses the hot aisle
containment as an example to describe how to install the end panels for cable troughs.
The end panels for cable troughs should be installed after the end doors are installed;
otherwise, the end doors may fail to be installed.
Issue Draft A (2015-06-29)
4.8.1 Installing a 600 mm Wide Cable
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Hardware Installation
Trough.
94