Intelligent micro-modular data center 2000 mm high cabinet in dual-row aisle containment
Hide thumbs Also See for IDS2000:
Table of Contents

Advertisement

IDS2000 Intelligent Micro-Modular Data Center
Installation Guide (2000 mm High Cabinet in Dual-Row
Aisle Containment)
Drainpipes should be able to withstand a temperature greater than 100º C; otherwise, pipe
deformation may occur (for equipment configured with a humidifier).
Drainpipes can be connected in two methods:
Determine the pipe connection method based on onsite pipes.
Figure 4-15 Connecting the drainpipe
(1) Copper pipe: external diameter of 3/4 inch
(3) Hose: inner diameter of 3/4 inch; made of
EPDM or other material
(5) Rigid pipe connector: external diameter of
3/4 inch; connected to copper pipe of 3/4 inch
BSPP with inner threads
Water Quality Requirements
Issue Draft A (2015-06-29)
Rigid pipe: Secure one end of a hose to the device port and the other end to a connector
using hose clamps. Then connect the other end of the connector to a rigid pipe with
external threads, as shown by method 1 in
Hose: Secure a hose to the device ports, as shown by method 2 in
Component 1 (inside the dotted box) is a port on the equipment. Components 2 and 4 are mandatory.
Other components are not provided.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Hardware Installation
Figure
4-15.
Figure
(2) Hose clamp
(4) Hose: inner diameter of 3/4 inch; made
of EPDM or other material
(6) Rigid pipe: made of PP-R, C-PVC, or
other material; with 3/4 inch BSPT
connector with external threads
4-15.
31