Huawei IDS2000 Installation Manual page 47

Intelligent micro-modular data center 2000 mm high cabinet in dual-row aisle containment
Hide thumbs Also See for IDS2000:
Table of Contents

Advertisement

IDS2000 Intelligent Micro-Modular Data Center
Installation Guide (2000 mm High Cabinet in Dual-Row
Aisle Containment)
Figure 4-23 Placing the air conditioner onto a base
Step 2 Installing enclosure frames for half-sized NetCol5000-A020 air conditioners. The BOM
number is 52271152. Fix enclosure frames onto the front door frame using six M6 screws
(two for the top two holes, and four for the bottom holes) and sixteen M4 screws, as shown in
Figure
Issue Draft A (2015-06-29)
4-24.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Hardware Installation
39