Function
The toggle switches are both
NO by default. Set both
toggle switches to NO if
you need to open the
skylight after the skylight
magnetic lock is energized.
Set both toggle switches to
NC if you need to open the
skylight after the skylight
lock is de-energized.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
A Appendix
Scenario Example
For a skylight lock with a
bolt, the 1 (+ –) to 14 (+ –)
ports of the skylight
controller do not supply
power to the bolt under
normal conditions. After
you press the skylight open
button or start remote open,
the 1 (+ –) to 14 (+ –) ports
supply power to the bolt.
Then the bolt draws in and
the skylight opens.
Take a skylight magnetic
lock for example. Normally,
the 1 (+ –) to 14 (+ –) ports
of the skylight controller
supply power to the lock.
After you press the skylight
open button or start remote
open, the 1 (+ –) to 14 (+ –)
ports do not supply power to
the magnetic lock. Then the
magnetic force of the
magnetic lock disappears
and the skylight opens.