Huawei IDS2000 Installation Manual page 86

Intelligent micro-modular data center 2000 mm high cabinet in dual-row aisle containment
Hide thumbs Also See for IDS2000:
Table of Contents

Advertisement

IDS2000 Intelligent Micro-Modular Data Center
Installation Guide (2000 mm High Cabinet in Dual-Row
Aisle Containment)
3.
Step 3 Secure screws for door posts.
1.
2.
----End
Issue Draft A (2015-06-29)
Figure 4-76 Door panel tilting down
If door panels mismatch, you can adjust the fastening screws between the posts and
cabinets or between the posts and skylight connective plates, and insert spacers so that
the door panels match, as shown in
loosened screws are tightened.
Figure 4-77 Adding spacers
Tighten the screws connecting the door posts and the skylights.
Secure the posts to the floor using the tapping screws delivered with the door panels.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
4-77. After adjustment, verify that all
4 Hardware Installation
78