When laying out the water detection cable, ensure that the water detector is close to the
network cabling cabinet to facilitate further cable connections.
Step 7 Place the water detection cable onto the fastener, secure the fastener, and keep the water
detection cable in close contact with the floor, as shown in
Figure 4-166 Securing a water detection cable
----End
Follow-up Procedure

4.12 Cable Routing

4.12.1 System Cabling Rules

The rules described in this section help you rapidly and properly route, bind, and connect
cables.
Requirements for Neatly Routing and Binding Cables
To route and bind cables in an appealing way, follow these rules:
1.
Issue Draft A (2015-06-29)
If several water detection cables are connected in series, connect the male connector of one cable to the
female connector of another cable.
For air supplied from under the floor: Put the water detector through the raised floor or
base to facilitate further cable connections.
For air supplied horizontally: Place the water detector on the floor to facilitate further
cable connections.
Neatly organize exterior cables in a large bundle of cables and prevent cable tangles that
are avoidable, as shown in