Installing A Wlds900 Water Detector - Huawei IDS2000 Installation Manual

Intelligent micro-modular data center 2000 mm high cabinet in dual-row aisle containment
Hide thumbs Also See for IDS2000:
Table of Contents

Advertisement

IDS2000 Intelligent Micro-Modular Data Center
Installation Guide (2000 mm High Cabinet in Dual-Row
Aisle Containment)
Procedure
Step 1 Put the cable of the audible and visual alarm through the cable hole on the end door upper
frame installation kit (as shown by (1) in
controller when connecting skylight controller cables later.
Step 2 Align the audible and visual alarm with the two mounting holes, and secure them using two
M3x16 pan head screws, as shown in
Figure 4-161 Installing the audible and visual alarm
(1) Cable hole
----End

4.11.13 Installing a WLDS900 Water Detector

Prerequisites
Context
Issue Draft A (2015-06-29)
Ensure that the side in red faces upward.
If air is supplied from under the floor, a cofferdam has been installed around the air
conditioners.
If air is supplied horizontally, the modular data center has been completely installed.
A water detector consists of a water detection cable, water detector, and conversion cable.
The water detection cable is laid out on the floor and connected to the water detector
placed near the collector by the conversion cable.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
4-161), and connect it to the skylight
Figure
4-161.
Figure 4-162
4 Hardware Installation
shows the components.
133