Huawei IDS2000 Installation Manual page 64

Intelligent micro-modular data center 2000 mm high cabinet in dual-row aisle containment
Hide thumbs Also See for IDS2000:
Table of Contents

Advertisement

IDS2000 Intelligent Micro-Modular Data Center
Installation Guide (2000 mm High Cabinet in Dual-Row
Aisle Containment)
When securing the skylight, place the spring pins in the lower right corner of the skylight
connective plates into holes on the top of cabinets to prevent skylight rotation during bolt
tightening.
When securing the skylight, ensure that the arrow of the Keep direction label on the
skylight points to the PDU8000.
1.
2.
Issue Draft A (2015-06-29)
Figure 4-46 Securing a flat skylight
Install a rotating skylight:
A skylight in the package is folded. Rotate the skylight connective plates to expand the
skylight in a door structure. For details, see
Lift the rotating skylight to the top of the aisle and secure the skylight to the cabinets
using four M12x30 bolts, as shown in
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4.6.2 Skylight
Overview.
Figure
4-47.
4 Hardware Installation
56