Huawei IDS2000 Installation Manual page 94

Intelligent micro-modular data center 2000 mm high cabinet in dual-row aisle containment
Hide thumbs Also See for IDS2000:
Table of Contents

Advertisement

IDS2000 Intelligent Micro-Modular Data Center
Installation Guide (2000 mm High Cabinet in Dual-Row
Aisle Containment)
Figure 4-89 Installing a conversion bracket
Figure 4-90 Installed cable tray (unit: mm)
Ensure that the front of the cable ladder is 535 mm away from the front of the base, as shown in
4-90.
Step 4 Connect ground cables.
1.
2.
Route the ground cable from the base into the cabinet through the cable hole on the top of the cabinet
and connect the cable to the mounting kit on the upper beam, as shown in
Issue Draft A (2015-06-29)
Connect ground cables between the cable ladder and base. M8 and M6 ground screws
are respectively used on the two sides, as shown by (1) in
Connect the M6 ground screws in the base and cabinet, as shown by (2) in