Huawei IDS2000 Installation Manual page 161

Intelligent micro-modular data center 2000 mm high cabinet in dual-row aisle containment
Hide thumbs Also See for IDS2000:
Table of Contents

Advertisement

IDS2000 Intelligent Micro-Modular Data Center
Installation Guide (2000 mm High Cabinet in Dual-Row
Aisle Containment)
Connecting Battery Cables
Issue Draft A (2015-06-29)
When the length of a battery cable equals the distance between two battery terminals,
connect the cable straight through, as shown in
Figure 4-188 Directly connecting two batteries
When the length of a battery cable is longer than the distance between two battery
terminals, connect the cable in the way shown in
battery terminals, do not connect the cable in the way shown in
Figure 4-189 Correct battery cable connection method
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Hardware Installation
Figure
4-188.
Figure
4-189. To prevent misshaping
Figure
4-190.
153