Huawei IDS2000 Installation Manual page 50

Intelligent micro-modular data center 2000 mm high cabinet in dual-row aisle containment
Hide thumbs Also See for IDS2000:
Table of Contents

Advertisement

IDS2000 Intelligent Micro-Modular Data Center
Installation Guide (2000 mm High Cabinet in Dual-Row
Aisle Containment)
Step 2 Remove the PDU8000 rear door, bolt fixing plate, rear door mounting kit, connection plates,
and ground screws.
Put aside the removed bolt fixing plate, rear door mounting kit, connection plates, and ground screws.
They will be installed on the tail frame.
Figure 4-27 Remove bolt fixing plate, rear door mounting kit, connection plates, and ground
screws
Step 3 Secure the tail frame at the back of the PDU8000 using two M6 screw assemblies at the top of
the tail frame and eight M5 tapping screws on the left and right sides of the tail frame, as
shown in
Issue Draft A (2015-06-29)
Figure
4-28.