Figure 4-160 Installing temperature sensors
----End

4.11.12 Installing the Audible and Visual Alarm

Context
By default, only one audible and visual alarm is provided for each module.
The audible and visual alarm must be installed on the visible side close to the equipment room
door.
Issue Draft A (2015-06-29)
The temperature sensor needs to be secured on the cable behind it 20 mm away from the
sensor probe.
The temperature sensor must not be in touch with metal parts or cabinets.
Ensure that the temperature sensors are installed on the side without a PDU2000 on the
cabinet rear.
Keep the temperature sensors facing the inside of the cabinets to ensure accurate
measurement of cabinet interior temperatures.