IDS2000 Intelligent Micro-Modular Data Center
Installation Guide (2000 mm High Cabinet in Dual-Row
Aisle Containment)
(5) Four-core cable B
Secure terminal block A near the magnetic locks using cable ties.
2.
3.
4.
After connecting cables to terminal block B, place terminal block B near the emergency door release
button without securing it.
5.
(1) Double-door magnetic lock
Issue Draft A (2015-06-29)
Strip four-core cable A delivered with the device and connect it to the other end of
terminal block A used in 1. Then route the cables to the emergency door release button
according to
Figure
4-206.
Directly connect the yellow cable to binding post 2 on the back of the emergency door
release button and the other three to terminal block B delivered with the device.
4-205
shows the cable connections.
Strip four-core cable B delivered with the device and connect the yellow cable to binding
post 1 on the back of the emergency door release button and the other three to the other
end of terminal block B.
Route four-core cable B used in
controller in the network cabling cabinet according to
Figure 4-206 Cable connections for the emergency door release button
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
(6) Back of the emergency door release button
Figure 4-205
shows the cable connections.
Figure 4-205
shows the cable connections.
4
out of the aisle and finally to the access control
4 Hardware Installation
Figure
4-206.
(2) Terminal block A
Figure
169